Maintenance

To maintain output, the water level in the cylinder will slowly

move upwards, exposing new electrode to the water as the

electrodes become coated with minerals. Eventually, all of the

usable electrode surfaces will be coated and the cylinder will be

full of water. At this point, the output will begin to drop and the

red “service” light will come on. The unit will shutdown. This indi-

cates the need to change the cylinder, typically 500-2000 hours

of operation, depending on the quality of the fill water supply.

To replace the cylinder

1. Drain cylinder completely using the ‘on-off- drain” switch.

2. Turn off power to the unit at the external disconnect. Dis-

connect electrode power wires (#38 & #39) and cylinder full

electrode wire (#29) from the tank. These connections are

1/4” quick connects. (See Figure 11B, 11C, & 11D)

3. Disconnect 1” hose at top of tank.

4. Remove tank, clean out the drain cup and insert the

Figure 11A

Figure 11C

new tank. Be sure that “o” ring is in place on the cylinder fill/

drain port prior to installation (See Figure 11A). New o-ring

is included with each replacement cylinder.

5. Clean and check both the fill and drain valves while servic-

ing the unit.

6. Check the strainer. If it is dirty or restricting the water-re-

place it.

7. Install cylinder in unit by pushing downward with a slight

twisting motion, while ensuring proper orientation of tank

within cabinet.

8. Reconnect electrode power wires (#38 & #39) and cylinder

full electrode, wire (#29). Make sure that all electrical con-

nections are securely tightened. (See Figure 11B, 11C, &

11D)

9. Follow cold start-up instructions on page 10. Monitor amp

draw for several cycles. .

Extended Shutdown

Always drain cylinder completely if unit will be off for an extend-

ed period of time. This will preserve the life of the cylinder.

Figure 11B

Figure 11D

CYLINDER FILL/DRAIN PORT

POWER WIRE CONNECTIONS

ELECTRODE CONNECTION

CYLINDER FULL ELECTRODE CONNECTION

PROTECTIVE BOOT

(SHOWN TRANSPARENT FOR CLARITY)

(SHOWN TRANSPARENT FOR CLARITY)

PROTECTIVE BOOT

GROMMET

1/4" LOCK WASHER

RED POWER WIRE

1/4"-20 NUT

1/4"-20 NUT

BLACK POWER WIRE

1/4" LOCK WASHER

EST-1060-3

O-RING

1/4" MALE

QUICK CONNECT

1/4" MALE

QUICK CONNECT

CYLINDER FULL

ELECTRODE

WIRE #29

POWER

WIRE #39

POWER

WIRE #38