beautypg.com

Installation, Control box mounting, Duct collar mounting – Greenheck Temperature Interlock (471738) User Manual

Page 3: Thermostat installation - hood mounting

background image

3

Temperature Interlock

Installation

Control Box Mounting

Locate an area with enough space to mount the control
box and fasten to the wall. Avoid installing the control
box in environments with high magnetic and/or radio
frequency interference.

3. Place the junction box provided over the fitting on

top of the hood, keeping the fitting centered in the
box.

4. Thread the thermostat into the compression seal

fitting and tighten to 35 ft-lbs.

(4.84 m-kgs)

.

Hood Plan View

19.525 inches

3 inch air space

2 inch typical

Exhaust Area

Supply Area

(optional)

Sensor Install

(cut out area)

1. Locate the flat

area(s) at the top
interior of the hood
in front of the
filters, towards the front
of the hood. A 1

1

8

to

1¼ inch (

28.58 to 31.75

mm)

diameter hole must

be cut into the top of
the capture tank. Make
sure the thermostat will
not interfere with the fire system nozzles and is not
within 8 inches

(20.32 cm)

of the light fixtures.

Hood Surface

(28.58 to 31.75 mm)

2. Insert the Evergreen Compression Seal fitting into

the hole from the inside of the hood, making sure the
gasket is placed on the fitting before inserting it into
the hole. Install the lock washer and 1

1

2  

inch

(38 mm)

nut on the threaded portion of the compression seal
fitting and tighten securely.

Exploded View (Components)

Gasket

Compression Seal

PN 452614

Nut

Lock Washer

Octagon Extension

PN 830125

Junction Box Plate

PN 732396

Duct Collar Mounting

1. Locate the exhaust duct on top of the hood. A 1

1

8

 to

1¼-inch

(28.58 to 31.75 mm) diameter

hole must be

cut into the duct 2 inches

(50.8 mm)

above the hood

top. Center the hole along the side of the duct. Make
sure that the thermostat will not interfere with any
fire system nozzles, or other items installed in the
exhaust duct. If an exhaust fire damper is present
the hood exhaust collar, it must be removed prior to
thermostat installation.

2. Insert the Evergreen Quik-Seal fitting into the hole

from the inside of the duct, making sure the gasket is
placed on the fitting before inserting it into the hole.
Install the lock washer and 1

1

inch

(38.1 mm)

nut

on the threaded portion of the Evergreen Quik-Seal
fitting and tighten securely.

3. Place the junction box provided over the fitting

and tack weld the junction box to the exhaust duct
keeping the fitting centered in the box. (Welding
optional).

4. Thread thermostat into Evergreen Quik-Seal fitting

and tighten to 35 ft-lbs

(4.84 m-kgs)

.

Gasket

1/2 inch Quik-Seal

PN 451168

Nut

Lock Washer

Octagon Extension

PN 830125

Junction Box Plate

PN 732396

Exploded View (Components)

2 inches

(50.8 mm)

Hood Exhaust Collar
(front side)

(28.58 to 31.75 mm)

NOTE

Control box may be factory mounted. If so, continue
to the next section.

Thermostat Installation - Hood Mounting

Recommended thermostat mounting location is in the
flat interior of the hood and at least 8 inches

(20.32 cm)

from light fixture.

NOTE

All field installation and wiring of electrical equipment
must be done to meet NEC and local codes.

®