Sidewall Propeller Fans

6

PROBLEM

CAUSE

CORRECTIVE ACTION

Too much airflow

Resistance lower than designed Decrease fan speed.

Reduced airflow

System resistance too high

Check backdraft dampers for proper operation. Remove
obstructions in ductwork. Clean dirty filters. Check for adequate
supply air for exhaust fans or exhaust air for supply fans.

Fan too close to damper

Increase distance between fan and damper.

Fan speed too low

Increase fan speed.

Excessive dirt buildup on
propeller

Clean propeller.

Excessive noise

Bearings

Tighten collars and fasteners. Lubricate bearings. Replace
defective bearings.

V-belt drive

Tighten pulleys on motor and fan shaft. Adjust belt tension. Align
pulleys properly. Replace worn belts or pulleys. See Maintenance.

Excessive vibration

Clean dirt buildup from propeller. Check all setscrews and
fasteners for tightness. Check for worn bearing. Correct propeller
imbalance. Check for loose dampers, guards or ductwork.

Defective motor

Replace motor.

Variable frequency drive (VFD)

Check VFD for drive setting, some controllers are able to be
adjusted to lower the harmonic noises sometimes heard during
operation by adjusting a simple setting on the controller.

Debris

Remove all debris from the fan.

Fan does not operate

Electrical supply

Check fuses/circuit breakers. Check for switches turned off or
disconnected. Check for correct supply voltage.

Drive

Check for broken or worn belts. Tighten loose pulleys.

Motor

Assure motor is correct horsepower and not tripping overload
protector.

Job Information

Job Name: ___________________________________ Service Organization: __________________________________

Address: _____________________________________ Address: _____________________________________________

City: ________________________________________ City: _________________________________________________

State:

_______________ Zip:

__________________ State: _______________ Zip:

__________________________

Phone: ______________________________________ Phone: ______________________________________________

Contact Person: ______________________________ Work Done By: _______________________________________

Nameplate Information

Field Start-Up Documentation

Model: ______________________________________

Volts:

_________ Hertz:

________ Phase:

______ Actual

Voltage:

_______ Hertz:

______ Phase:

_________

Amps: _______________ Mark: ________________ Actual Amperage: _____________________________________

Supply hp: ___________ Exhaust hp: ___________ Blower

Rotation:

______________________________________

Serial Number: _______________________________ Air Volume:

Design cfm: _____________________________

Model Voltage: _______________________________

Actual cfm: ______________________________

Motor Amperage: _____________________________ Level of fan (L or H): ___________________________________

Fan RPM: ____________________________________ Fan RPM Range (min.) ____________ (max.) _____________

WARNING

Before taking any corrective action, make certain
unit is not capable of operation during repairs.

AVERTISSEMENT

Avant d’entreprendre toute action corrective,
s’assurer que l’appareil ne pourra pas fonctionner
durant les réparations.

Troubleshooting

Maintenance Documentation

®