Utility and Centrifugal Fans

6

®

Ducted Outlet Installations

Discharge Duct Turns - Duct turns located near the
fan discharge should always be in the direction of the
fan rotation.

Fan performance is reduced when duct turns
are made immediately off the fan
discharge. To achieve cataloged fan
performance there should be at least
three equivalent
duct diameters of
straight ductwork
between the fan
discharge and
any duct turns.

Non-Ducted Installations

Inlet Clearance - Installation of a fan with an open
inlet too close to a wall or bulkhead will cause
reduced fan performance. It is desirable to have
a minimum of three-fourths of a wheel diameter
between the fan inlet and the wall.

Free Discharge - Free or abrupt discharge into a
plenum results in a reduction in fan performance. The
effect of discharge static regain is not realized.

R

o

ta

tion

R

o

ta

tion

POOR

Length of Straight Duct

GOOD

3/4 to one

fan

wheel

diameter

Single Fan Installation

Inlet Spin - Inlet spin is a frequent cause of reduced
fan performance. The change in fan performance is a
function of the intensity of spin and not easily defined.
The best solution is proper duct design and airflow
patterns. Turning vanes reduce the effects of inlet
spin.

Rota

tio

n

Rota

tio

n

Turning

Vanes

POOR

GOOD

Turning

Vanes

GOOD

Three fan wheel diameters

Installations with inlet or discharge configurations
that deviate from this manual may result in reduced
fan performance. Restricted or unstable flow at the
fan inlet can cause pre-rotation of incoming air or
uneven loading of the fan wheel yielding large system
losses and increased sound levels. Free discharge
or turbulent flow in the discharge ductwork will also
result in system effect losses. Refer to the following
diagrams for the most efficient installation conditions.

Ducted Inlet Installations

Inlet Duct Turns - Installation of a duct turn or elbow
too close to the fan inlet
reduces fan performance
because air is loaded
unevenly into the fan
wheel. To achieve full
fan performance, there
should be at least three
fan wheel diameters
between the turn or
elbow and the fan inlet.

POOR