Greenheck PVe (472846) User Manual
Page 18

18
Model PVe Heat Recovery Unit
MODULATING CONTROL FOR FAN SPEED
(0-10 VDC)
Parameter
Setting
V1000
J1000
A1-01
Access Level
2
2
b1-17
VFD Start-Up Setting
1
1
C1-01
Acceleration Time
30 sec.
30 sec.
C1-02
Deceleration Time
30 sec.
30 sec.
C6-02
Carrier Frequency
1
1
d2-02
Ref Lower Limit
50%
50%
E2-01
Motor Rated FLA
Motor
FLA
Motor
FLA
H3-04
Terminal A1 Bias
50%
50%
A1-01
Access Level
0
0
MULTI-SPEED CONTROL FOR FAN SPEED
(1/3 OR 1/2 SPEED REDUCTION)
Parameter
Setting
V1000
J1000
A1-01
Access Level
2
2
b1-01
Reference Source (Frequency)
0
0
b1-17
VFD Start-Up Setting
1
1
C1-01
Acceleration Time
30 sec.
30 sec.
C1-02
Deceleration Time
30 sec.
30 sec.
C6-02
Carrier Frequency
1
1
d1-01
Frequency Reference 1
60 Hz
60 Hz
d1-02
Frequency Reference 2
40 Hz
40 Hz
d1-03
Frequency Reference 3
30 Hz
30 Hz
d1-04
Frequency Reference 4
60 Hz
60 Hz
d2-02
Ref Lower Limit
50%
50%
E2-01
Motor Rated FLA
Motor
FLA
Motor
FLA
H1-04
Multfunction Input Sel 4
(Terminal S4)
3
3
H1-05
Multifunction Input Sel 5
(Terminal S5)
4
4
H1-06
Multifunction Input Sel 6
(Terminal S6)
5
NA
H3-10
A2 Not Used
F
NA
A1-01
Access Level
0
0
CO
2
SENSOR CONTROL FOR FAN SPEED
(1/2 SPEED WHEN C0
2
DROPS BELOW 700 PPM)
(FULL SPEED WHEN C0
2
RISES ABOVE 800 PPM)
Parameter
Setting
V1000
J1000
A1-01
Access Level
2
2
b1-01
Reference Source (Frequency)
0
0
b1-17
VFD Start-Up Setting
1
1
C1-01
Acceleration Time
30 sec.
30 sec.
C1-02
Deceleration Time
30 sec.
30 sec.
C6-02
Carrier Frequency
1
1
d1-01
Frequency Reference 1
60 Hz
30 Hz
d1-02
Frequency Reference 2
30 Hz
60 Hz
d2-02
Ref Lower Limit
50%
50%
E2-01
Motor Rated FLA
Motor
FLA
Motor
FLA
H3-10
A2 Not Used
F
NA
A1-01
Access Level
0
0