Troubleshooting, Motor overamps, Too much airflow – Greenheck IGK (472084) User Manual
Page 12

12
Model IGK Make-Up Air
®
Motor Overamps
Troubleshooting
Air volume too high?
Adjust drives or increase external
static pressure as needed.
(Reference Blower Start-Up step #5)
Motor horsepower too low?
Resize motor.
Motor voltage correct?
Provide proper power supply.
(Reference Blower Start-Up step #1)
Blower rotation correct?
Reverse blower rotation.
(Reference Blower Start-Up step #2)
Actual static pressure
lower than design?
Adjust drives to reduce blower RPM.
(Reference Blower Start-Up step #5)
No
No
Yes
Yes
Yes
Yes
No
Yes
No
No
Shorted windings in motor?
Replace motor.
Yes
Everything is working
properly, consult factory.
Yes
Too Much Airflow
Blower speed too high?
Adjust drives as needed.
(Reference Blower Start-Up step #5)
Insufficient external static
pressure?
Increase external static pressure.
Filters not in place?
Install filters.
Yes
Yes
Yes
No
No
Everything is working properly,
consult factory.
No