Housed Plenum Array, Plug and Plenum

One-half

wheel

diameter

One-half

wheel

diameter

One-half

wheel

diameter

One

wheel

diameter

Installation - Plenum and Plug Fans

Unhoused Wheels

Adjacent Walls - The distance between the fan and
walls or ceilings will effect the performance of the fan.
The recommended distance between the fan wheel
and any wall is a minimum of one-half wheel diameter.
Multiple walls reduce the performance even more.

Side by Side - When two or more plenum fans are
in parallel, there should be at least one fan diameter
spacing between the wheels. Applications with less
spacing will experience performance losses.

CAUTION

When installing a fan, ensure the proper protective
devices are used to protect personnel from moving
parts and other hazards. A complete line of protective
accessories are available from Greenheck including
inlet guards, outlet guards, belt guards, shaft guards,
protective cages, and electrical disconnects.

Wheel

Size

Standard Housing

W

H

D^

Maximum

Stacked

Modules

Maximum

Motor

Frame

Weight*

(lbs.)

15

29.00 29.00 32.06

4

215T

215

16

31.50 31.50 37.00

256T

250

18

34.38 34.38 38.19

3

256T

290

20

37.25 37.25 39.56

256T

340

22

41.00 41.00 42.19

286T

380

24

44.75 44.75 43.75

286T

425

27

48.94 48.94 47.56

2

286T

680

30

53.81 53.81 48.94

326T

820

33

58.81 58.81 51.06

326T

960

36

64.56 64.56 51.06

326T

1100

Dimensions are in inches.
^Does not account for motors or accessories.
*Weight is less motor and drives.

Installation - Housed Plenum Array

3. Bolt the fan to the floor and

adjacent fans using the inlet
and outlet mounting flanges.
The first layer of fans should
be securely installed before
installing the second layer of
fans.

4. Thin gasket material or caulk between fans is

recommended to prevent unwanted noise of air.

5. Do not exceed the maximum number of stacked

modules (refer to table).

1. Carefully remove any crate

and packing materials.

2. Place the fan onto the

mounting structure using
the recommended lifting
points and hooking
method as shown. Lift
each fan individually into
it’s proper position.