Range element disconnect installation – Greenheck Fire Ready Hood - GRRS User Manual

Page 10

background image

10

Fire Ready Hood

Gas Disconnect Valve (if applicable)

The gas solenoid is designed for use with 3/4-inch NPT
pipe. Be sure to note the “IN” and “OUT” ends of the
solenoid body (as marked on the body). This determines
direction of gas flow. Refer to wiring diagram on pages
13 and 15 for details on electrical connection.

Electrical Disconnect Box (if applicable)

1. Cut a hole in the drywall for the relay box; refer to

the submittal for dimensions. Be sure to note the
1-1/4 inch overhang on each side of the face plate.
Given this, the hole should be about 6-3/8 by 8-3/4
inch. The relay box has been designed to fit in a
standard 2x4 studded wall.

2. If you haven’t already done so, run wiring from the

junction box location (on the unit mounting plate) to
the power disconnect box location and string through
one of the knockouts in the box.

3. Make all wiring connections and secure face plate to

box in wall. Wiring information is provided on pages
13 and 15.

Range Element Disconnect Installation

Face Plate

208-220 VAC

supply to appliance

120 VAC

from hood, black tape

120 VAC

from hood, black tape

6-3/8 in.

8-3/4 in.

110 VAC Supply from Hood
- Electrical Connection

3/4-in. NPT

3/4-in. NPT

GAS FL

OW

®