Installation - arrangement db / hz – Greenheck DG / DGX with Direct Spark (464043 IOM) (Pre-2008) User Manual
Page 4
![background image](https://www.manualsdir.com/files/787990/content/doc004.png)
4
Step 6 Seal Weatherhood Seam
Using an appropriate sealant, seal the seam between
the weatherhood and the unit.
Step 3 Apply Sealant
Apply an appropriate sealant around the perimeter of
the curb and duct adapter(s) to isolate fan vibration
and prevent water penetration.
Step 1 Install Curb and/or Equipment
Support(s)
Position curb/equipment support(s) on the roof
(reference the CAPS submittal for placement of
curb/equipment support(s) in relation to the unit).
Verify that unit supports are level, shim if necessary.
Attach curb to roof and flash into place. Attach the
equipment support(s) to the roof, remove metal cover,
flash to wooden nailer and reinstall cover.
Step 2 Install Ductwork
Good duct practices should be followed for all
ductwork. All ductwork should be installed in
accordance with SMACNA and AMCA guidelines,
NFPA 96 and all local codes. Reference the CAPS
submittal for ductwork sizes.
Step 4 Install Unit
Use a crane and a set of spreader bars hooked to the
factory lifting lugs to lift and center the unit on the
curb/equipment support(s).
Use self-tapping sheet metal screws to fasten the unit
to the curb/equipment support(s).
Step 5 Assemble and Attach
Weatherhood
The weatherhood can now be assembled and
attached to the unit. Detailed assembly instructions
can be found with the weatherhood. If the optional
evaporative cooling module was selected, this step
does not apply, refer to the installation instructions for
the optional evaporative cooling module.
Supply Air Ductwork
(Arrangement DB only)
Optional Return Air Duct
(Arrangement HZ and DB)
Sealant
Installation - Arrangement DB / HZ
Installation
NOTE!
The use of all lifting lugs and a set of spreader
bars is mandatory when lifting the unit.
NOTE!
Some units come with the weatherhood attached
and step 5 may not apply.
NOTE!
The use of a duct adapter is recommended on a
downblast (DB) arrangement to align the
ductwork with the supply unit. The duct adapter
is only a guide and is not to be used as support
for the ductwork.
Metal Cover
Equipment
Support
Roof Curb
Roof Curb
Ductwork
Setting Unit
Complete Rooftop Installation