beautypg.com

Installation - indoor installation – Greenheck DG / DGX with Direct Spark (464043 IOM) (Pre-2008) User Manual

Page 3

background image

3

Installation - Indoor Installation

Installation

Step 1 Install Hangers

Install threaded hangers from ceiling supports. When locating hangers, allow enough room to open access
panel(s). Two nuts must be used on the end of each threaded hanger. Ceiling supports are supplied by others.

Step 2 Install Unit

Using sheet metal screws, attach the
weatherhood/thru-wall/filter section to the
blower/burner section. The flange on the
weatherhood/thru-wall/filter section should overlap
the flange on the blower/burner section.

Raise the assembled unit into place.

Using two nuts per hanger, fasten the unit supports to
the hangers under the unit. Appropriate unit supports,
such as the optional Greenheck hanging bracket kit
or c-channel and angle iron (supplied by others)
should be used.

Using self-tapping screws, attach ductwork to unit.

In order to prevent the unit from swinging and to
provide a safe environment for service and
maintenance, additional measures must be taken to
secure the unit in all directions.

Step 3 Seal Wall Opening

Apply sealant around the perimeter of the
weatherhood to prevent water penetration and drafts
into the building.

NOTE!

Two nuts must be used on each end of each

threaded hanging rod for proper support.

NOTE!

Good duct practices should be followed for all ductwork. Ductwork should be installed in accordance

with SMACNA and AMCA guidelines, NFPA 96 and any local codes. Reference the CAPS submittal for

duct sizes.

Sealant

Unit

Supports

Ceiling

Supports

Hangers

Ductwork

Indoor Mounting

Sealing Wall Opening

This manual is related to the following products: