Zone Pressure Touch (ZPT) Sensor - Standard Range

Installation and Operation Instructions

rev. 05/09/2014

Specifications subject to change without notice.

DISPLAY ON OR OFF

Setting the display to “on” allows the display to show the current pressure reading during normal operation. Setting

the display to “OFF” prevents a casual observer from seeing the pressure reading during normal operation. All the

observer will see is the word “On,” indicating that the pressure transmitter is functional. A knowledgeable user can

display the pressure range endpoints, current pressure reading, and the output percent of span by pressing the

arrow or enter buttons as described on page 3 in the Normal Operation “Additional Features” section.

Entry Icon

• Enter the Display On or Off Mode as described in the “Entering and Exiting Parameter Setup Mode” on the page

3.

• Press and release the enter button. The display will show the current display state, “On” or “OFF”. Using the

left or right arrow buttons, select the display state needed.

• Press and release the enter button. When the display shows “diSP,” the display mode is set and stored.
• Either resume normal operation or edit another parameter.

Parameter Setup continued...

POSSIBLE PROBLEMS:
LED does not light

Output not tracking pressure properly

POSSIBLE SOLUTIONS:
- Check power connections for proper power

- Remove pressure from ports and perform auto-zero procedure
- Check for proper pressure range selection
- Check for proper output range selection

Diagnostics