Upgradeable PDU Instruction Manual

30

© 2015 Geist

GM1157 - GU PDU Instruction Manual

subsequently returns to normal.

i. To determine where the alert notifications will be sent to when this particular

Alarm or Warning Event occurs, click the Add icon to create a new Action, then
select the desired options from the drop-down menu:

Target is the e-mail address or SNMP manager to which notifications should be sent
when the Event is tripped.
Delay determines how long this Event must remain tripped for before this Action's
first notification is sent. (Note that this is different from the Trip Delay, above; Trip
Delay
determines how long the threshold value has to be exceeded before the Event
itself is tripped; this delay determines how long the Event must remain tripped
before this Action occurs.) Delay can be up to 14400 seconds (4 hours). A Delay
of 0 will send the notification immediately.
Repeat detemines whether multiple notifications will be sent for this Event Action.
Repeat notifications are sent at the specified intervals until the Event is
acknowledged, or until the Event is cleared and reset. The Repeat interval can be
up to 14400 seconds (4 hours). A Repeat of 0 disables this feature, and only one
notification will be sent.

Then, click Save to save this notification Action.

More than one Action can be set for an Alarm or Warning; to add multiple Actions, just
click the Add icon again and set each one as desired. Each alert can have up to 32
Actions associated with it.

To change an existing notification Action, click the Modify icon next to the Action you
wish to change, then modify its settings as above.