Specifications


Overview

The Watchdog 100 provides remote environmental monitoring and alarming capability needed to
detect climate conditions in data centers. Additionally, the Watchdog 100 provides one output
relay that can be operated remotely or set to automatically open or close based on alarm
conditions. The Watchdog 100 is equipped with a built-in web server with a 10/100 Mbps
connection speed. Web pages are generated by the unit to monitor local environmental
conditions. No software other than a web browser is required for operation and several data
formats are available. The Watchdog 100 has a built-in sensor to monitor temperature, humidity
and dew point, as well as one port for adding remote sensors. The Watchdog 100 also has four
I/O ports for connecting additional external 5Vdc sensors such as Water and Door Sensors. The
Watchdog 100 can be optionally configured at the factory to support Power-Over-Ethernet (PoE).

Environmental

Temperature

Operating: 10°C (50°F) min

45°C (104°F) max

Storage:

-25°C (-13°F) min 65°C (149°F) max

Humidity

Operating:

5% min

95% max

(non-condensing)

Storage:

5% min

95% max

(non-condensing)

Elevation

Operating:

0 m (0 ft) min

2000 m (6561 ft) max

Storage:

0 m (0 ft) min

15240 m (50000 ft) max

Electrical

6-12 Volts DC, 2 Amps

Output Relay Contact Ratings

The output relay contacts are intended to carry low voltage signals only. Do not exceed the
following ratings on the output relay contacts:

DC: 60 V, 30 W

AC: 30 Vrms, 1 A

Warning:

Consideration should be given to lockout-tagout and other procedures

required for servicing external devices controlled by the Watchdog 100 output relays.
Appropriate safety precautions must always be taken when operating or maintaining
equipment connected to the Watchdog 100. Geist Manufacturing assumes no
responsibility or liability for any injury or damage to any persons or property resulting
from improper operation or maintenance of a device connected to the Watchdog 100.