Fitting string fuses

Safety

Selecting string
fuses

Select the string fuses to protect the solar modules in accordance with the module manu-
facturer's instructions or as described in the 'Criteria for selecting the correct string fuses'
section:
-

max. 20 A per fuse holder

-

max. 30 solar module strings

-

max. 50 A per measuring channel

-

max. 250 A total input current

-

Fuse dimensions: diameter 10 x 38 mm

IMPORTANT!
-

Note the safety requirements for the solar modules

-

Note the requirements of the solar module manufacturer

Fitting string fus-
es

WARNING! An electric shock can be fatal. Danger from DC voltage in solar mod-
ules.
-

Make sure that both the input side and output side of the device are de-ener-
gised before attaching any connections.

-

Never fit or remove fuses while under load.

-

All connections must be made by qualified electricians.

-

Note the safety rules in these operating instructions.

NOTE! Fit string fuses in the fuse holders according to the number of solar mod-
ules in use.