beautypg.com

Buswitch, With f – Flowserve BUSwitch User Manual

Page 3

background image

AXAIM020-01

(AUTO-48)

3/03

Page 3 of 16

© 2003, Flowserve Corporation, Printed in U.S.A.

BUSwitch

with F

OUNDATION

®

Fieldbus Protocol

Installation, Operating and Maintenance Instructions

Flowserve Corporation

1350 N. Mountain Springs Parkway

1978 Foreman Dr.

Flow Control Division

Springville, Utah 84663-3004

Cookeville, TN 38501

www.flowserve.com

Phone: 801 489 8611

Phone: 931 432 4021

Start-up Guide

CAUTION

The BUSwitch

may cycle during a configura-

tion download. Exercise caution in handling
valves that may be stroked during these
procedures.

For best results, Flowserve strongly recom-
mends reading this entire document before
attempting to configure and commission
BUSwitches.

1 Following the instructions in “Mechanical

Installation,” install the BUSwitch

onto a

pneumatic actuator and turn supply air on.

2. Following the instructions in “Electrical connec-

tions,” connect fieldbus and optional dry-contact
wiring.

3. Referring to control system or configuration system

documentation, install BUSwitch

device descrip-

tion (DD) files onto system hard drive. Note:
Readme file on DD floppy contains instructions.

Note: For Fisher DeltaV systems, the DD files
must be copied to a directory or folder named
“464C4F” in order for the system to find them.

4. Initialize communications with device and bring

up the “Live List.” BUSwitches have been
configured from the factory with an ID of
“464C4F5053:BUSWITCH: [serialnumber]” and
a default tag of “FLOWSERVE BUSWITCH.”
Note the serial number.

5. Change the BUSwitch

attribute Device ID to the

value noted in step 4 and change the Device Tag
to the appropriate value.

6. Assign the Tag configuration in step 5.

7. BUSwitches are shipped with resource block,

transducer block, (2) DO blocks and (2) DI blocks
pre-configured unless specially configured by
agreement with customer. Refer to the appropriate
sections in this manual for the default configuration.
Make any desired changes to this configuration
and download.

Power Requirements: Communications Card

XA0239
Communication Card

Bus powered
9.5-32 VDC at 18 mA

Power requirements: 2-Wire Version

XA0238 Interface
Card Version 2.0

Bus powered by
XA0239 Communication
Card

Power requirements

: 4-Wire Version

XA0242 Interface
Card

24 VDC

• 10 mA quiescent

510 mA max. with
solenoid activated

Temperature

Operational

-40°F to +185°F
(-40°C to + 85 °C)

Storage

-40°F to + 250°F
(-40°C to + 120°C)

To operate, an external 24 VDC source must be locally
supplied to the interface card.

Printed Circuit Board Specifications

F

OUNDATION

®

Fieldbus Information

Manufacturer
ID

464C4F (Hex)

Name

46 6C 6F 77 73 65 72 76 65

F l o w s e r v e

Device
Type

0x

0x

5053 (Hex)

ID

464C4F5053:BUSWITCH:xxxxxx
Max. length of 32 characters.
Characters 21 through 32 are
used for board serial number.

Device Descriptions are supplied on included
diskette