Buswitch, With f – Flowserve BUSwitch User Manual
Page 3
AXAIM020-01
(AUTO-48)
3/03
Page 3 of 16
© 2003, Flowserve Corporation, Printed in U.S.A.
BUSwitch
™
with F
OUNDATION
®
Fieldbus Protocol
Installation, Operating and Maintenance Instructions
Flowserve Corporation
1350 N. Mountain Springs Parkway
1978 Foreman Dr.
Flow Control Division
Springville, Utah 84663-3004
Cookeville, TN 38501
www.flowserve.com
Phone: 801 489 8611
Phone: 931 432 4021
Start-up Guide
CAUTION
The BUSwitch
™
may cycle during a configura-
tion download. Exercise caution in handling
valves that may be stroked during these
procedures.
For best results, Flowserve strongly recom-
mends reading this entire document before
attempting to configure and commission
BUSwitches.
1 Following the instructions in “Mechanical
Installation,” install the BUSwitch
™
onto a
pneumatic actuator and turn supply air on.
2. Following the instructions in “Electrical connec-
tions,” connect fieldbus and optional dry-contact
wiring.
3. Referring to control system or configuration system
documentation, install BUSwitch
™
device descrip-
tion (DD) files onto system hard drive. Note:
Readme file on DD floppy contains instructions.
Note: For Fisher DeltaV systems, the DD files
must be copied to a directory or folder named
“464C4F” in order for the system to find them.
4. Initialize communications with device and bring
up the “Live List.” BUSwitches have been
configured from the factory with an ID of
“464C4F5053:BUSWITCH: [serialnumber]” and
a default tag of “FLOWSERVE BUSWITCH.”
Note the serial number.
5. Change the BUSwitch
™
attribute Device ID to the
value noted in step 4 and change the Device Tag
to the appropriate value.
6. Assign the Tag configuration in step 5.
7. BUSwitches are shipped with resource block,
transducer block, (2) DO blocks and (2) DI blocks
pre-configured unless specially configured by
agreement with customer. Refer to the appropriate
sections in this manual for the default configuration.
Make any desired changes to this configuration
and download.
Power Requirements: Communications Card
XA0239
Communication Card
Bus powered
9.5-32 VDC at 18 mA
Power requirements: 2-Wire Version
XA0238 Interface
Card Version 2.0
Bus powered by
XA0239 Communication
Card
Power requirements
†
: 4-Wire Version
XA0242 Interface
Card
24 VDC
• 10 mA quiescent
•
510 mA max. with
solenoid activated
Temperature
Operational
-40°F to +185°F
(-40°C to + 85 °C)
Storage
-40°F to + 250°F
(-40°C to + 120°C)
†
To operate, an external 24 VDC source must be locally
supplied to the interface card.
Printed Circuit Board Specifications
F
OUNDATION
®
Fieldbus Information
Manufacturer
ID
464C4F (Hex)
Name
46 6C 6F 77 73 65 72 76 65
F l o w s e r v e
Device
Type
0x
0x
5053 (Hex)
ID
464C4F5053:BUSWITCH:xxxxxx
Max. length of 32 characters.
Characters 21 through 32 are
used for board serial number.
Device Descriptions are supplied on included