Buswitch, With f – Flowserve BUSwitch User Manual
Page 13

AXAIM020-01
(AUTO-48)
3/03
Page 13 of 16
© 2003, Flowserve Corporation, Printed in U.S.A.
BUSwitch
™
with F
OUNDATION
®
Fieldbus Protocol
Installation, Operating and Maintenance Instructions
Flowserve Corporation
1350 N. Mountain Springs Parkway
1978 Foreman Dr.
Flow Control Division
Springville, Utah 84663-3004
Cookeville, TN 38501
www.flowserve.com
Phone: 801 489 8611
Phone: 931 432 4021
Rel.
Index
Parameter Mnemonic
Data
Type
Size
Valid
Range
Units
Class
16
ACT_MODEL_NUM
Visible String
32
String Data
N/A
17
ACT_SN
Visible String
32
String Data
N/A
18
VALVE_MAN_ID
Unsigned 32
4
N/A
19
VALVE_MODEL_NUM
Visible String
32
String Data
N/A
20
VALVE_SN
Visible String
32
String Data
N/A
21
VALVE_TYPE
Unsigned 8
1
N/A
R/W
22
XD_CAL_LOC
Visible String
32
N/A
R/W
23
XD_CAL_DATE
Time of Day
7
N/A
R/W
24
XD_CAL_WHO
Visible String
32
N/A
R/W
25
OPERATION
Unsigned 8
1
1=Single
2=Double
N/A
R/W
R/W
R/W
R/W
R/W
R/W
26
OUTPUT_CONFIGURATION
Unsigned 8
1
1=Pulse
2=Constant
N/A
R/W
27
ODOMETER
Unsigned 32
4
N/A
Read
28
RESET_ODOMETER
Unsigned 8
1
True/False
N/A
R/W
29
FAILURE_RECOVER
Unsigned 8
1
1=Enabled
2=Disabled
N/A
R/W
30
RESET_TIMEOUTS
Unsigned 8
1
True/False
N/A
R/W
31
TRANSITION_TIME
Float
4
Sec.
Read
32
TIME_OUT
Float
4
Sec.
R/W
33
SOLENOIDE_CLOSED
Unsigned 8
1
True/False
N/A
Read
34
SOLENOIDE_OPENED
Unsigned 8
1
True/False
N/A
Read
35
TRANSITION_ALARM
Unsigned 8
1
True/False
N/A
Read
36
EXTERNAL_ALARM
Unsigned 8
1
True/False
N/A
Read
37
ACTION_TIME
Float
4
Sec.
Read
Abbreviations: R/W – Read/Write
Sec. – Seconds