Positioner Overview
The Logix 3200IQ digital positioner is a two-wire
4-20 mA input digital valve positioner. The positioner is
configurable through the local user interface. The Logix
3200IQ utilizes the HART protocol to allow two-way
remote communications with the positioner. The Logix
3200IQ positioner can control both double- and single-
acting actuators with linear or rotary mountings. The
positioner is completely powered by the 4-20 mA input
signal. Start up current must be at least 3.6 mA without
AO card or 3.85 mA with AO card.
Specifications
Table I: Electrical Specifications
Power Supply
Two-wire, 4-20 mA
10.0 to 30.0 VDC
Compliance Voltage
10.0 VDC @ 20 mA
495
Ω
@ 20 mA Typical
Effective Resistance
Add 20
Ω
when HART
communication active
Communications
HART Protocol
Minimum Operating
3.6 mA without AO board
Current
3.85 mA with AO board
Maximum Voltage
30.0 VDC
Table II: SoftTools Suite Software Specifications
Computer
Minimum Pentium processor running
Windows 95, 98, NT, 2000, XP, 32 MB
total memory (64 MB recommended),
30 MB available hard disk space,
CD-ROM drive
Ports
1 minimum available with 8 maximum
possible. (Can also communicate via
PCMCIA and USB connections)
HART Modem
RS-232/PCMCIA card/USB
HART Filter
May be required in conjunction with
some DCS hardware
HART MUX
MTL 4840/ELCON 2700
Table III: Environmental Conditions
Standard
-4° to 176°F
Operating Temperature
(-20° to 80°C)
Range
Low
-40° to 176°F
(-40° to 80°C)
Transport and Storage
Temperature Range
-40° to 176°F (-40° to 80°C)
Operating Humidity
0 to 100% non-condensing
Note: The air supply must conform to ISA Standard
ISA 7.0.01 (a dew point at least 18 degrees Fahrenheit
below ambient temperature, particle size below five
microns – one micron recommended – and oil content
not to exceed one part per million).
Table IV: Physical Specifications
Housing Material
Cast, powder-painted aluminum,
stainless steel
Soft Goods
Buna-N / Fluorosilicone
Weight
8.3 pounds (3.9 kg) aluminum
20.5 pounds (9.3 kg) stainless steel
Table V: Positioner Specifications
Deadband
<0.1% full scale
Repeatability
<0.05% full scale
Linearity
<0.5% (rotary), <0.8%,
(sliding stem) full scale
Air Consumption
<0.3 SCFM (0.5 Nm
3
/hr)
@ 60 psi (4 barg)