Wiring – Flowserve NRG16-41 User Manual
Page 19

9
■
Wire equipment in series. Star-type wiring is not permitted.
■
Interlink screens of control cables such that electrical continuity is ensured and
connect them
once to the central earthing point (CEP).
■
The first and last equipment of a CAN bus network
must be provided with a
terminating resistor of 0
Ω. Fig. 13
■
The CAN bus network must
not be interrupted while operating.
An interruption will result in high/low level alarm!
Tools
Attention
■
Screwdriver for cross head screws, size
■
Screwdriver for slotted screws, size .5, completely insulated according to VDE 0680
■
Open-end spanner 7 mm A. F.
Wiring
continued
This manual is related to the following products: