Maintenance, Error code – Flowserve OR 52-5 User Manual
Page 31
31
Maintenance
continued
Indication of Error Code
In the event of a malfunction the yellow LED Malfunction
lights up, the relay output Malfunction opens and the
7-segment display indicates the error code.
The raising of an alarm is not effected by a malfunction.
Error Code Table
Error code
Possible reason
Remedy
E 01
Glow lamp in light emitter
contaminated
Replace glow lamp
Glass cylinder
contaminated
Clean or replace glass cylinder
Turbidity of fluid too high
Provide mechanical cleaning stage
ahead of equipment
Operating voltage too low
Check supply voltage
Cleaning device
not in its initial
position
Return cleaning device
to its
initial position
Ingress of solids
Provide mechanical cleaning stage
ahead of equipment