beautypg.com

Flowserve 510si Series Digital Positioner User Manual

Page 8

background image

8

®

User Instructions Logix 510si - LGENIM0510-0

2 12/13

NOTE: The switch settings in the Configuration box
are activated only by pressing the Quick-Cal button.

Operation of CONFIGURATION DIPswitch Setup -The
first 5 DIP Switches are for basic configuration.

a. Air

Action

- This must be set to match the configuration

of the valve/actuator mechanical tubing connection and
spring location since these determine the air action of
the system.

Ê

ATO (air-to-open)- Selecting ATO if increasing
output pressure from the positioner is tubed so

it will cause the valve to open.

Ê

ATC (air-to-close)- Selecting ATC if increasing
output pressure from the positioner is tubed so

it will cause the valve to close.

b.

Signal at Closed - Normally this will be set to 4 mA for
an Air-to-open actuator, and 20 mA for an Air-to-close
actuator configuration.

Ê

UÊ -iiV̈˜}Ê{ʓÊ܈Ê“>ŽiÊ̅iÊÛ>ÛiÊvՏÞÊVœÃi`ÊÊ
when the signal is 4mA and fully open when the

signal is 20 mA.

Ê

UÊ -iiV̈˜}ÊÓäʓÊ܈Ê“>ŽiÊ̅iÊÛ>ÛiÊvՏÞÊVœÃi`ÊÊ
when the signal is 20 mA and fully open when

the signal is 4 mA.

c. Characteristic
Ê

UÊ -iiVÌʈ˜i>ÀʈvÊ̅iÊ>VÌÕ>̜ÀÊ«œÃˆÌˆœ˜ÊŜՏ`ÊLiÊÊ

directly proportional to the input signal.

Ê

UÊ /…iÊr¯Êœ«Ìˆœ˜Ê܈ÊV…>À>VÌiÀˆâiÊ̅iÊ>VÌÕ>̜ÀÊÊ
response to the input signal based on a stan-

dard 30:1 equal percent rangeability curve.

d. Tight

Shutoff

Ê

UÊ -iiVÌÊ"˜Ê̜ʅ>ÛiÊ̅iÊ«œÃˆÌˆœ˜iÀÊvՏÞÊÃ>ÌÕÀ>ÌiÊÊ

the actuator closed at a signal less than 1%.

Ê

UÊ -iÌ̈˜}Ê̅iÊÃ܈ÌV…ʈ˜Ê̅iÊ"vvÊ«œÃˆÌˆœ˜Ê`ˆÃ>LiÃÊÊ
this

feature.

e. Auto

Tune -This switch controls whether the positioner

will auto tune itself every time the quick cal button is
pressed

On enables an automatic tuning feature that will auto-
matically determine the positioner gain settings every
time a “Quick-Cal” is performed. The gain settings can
be modified after a calibration by adjusting the rotary
“Gain” switch.

NOTE: there is a small black arrow indicating the selec-
tion. The slot does not indicate the chosen gain.

Figure 4: Logix 510si Local Interface

Configuration
Switches

Gain selector

4-20 mA Input

4-20 mA Feedback
(Optional)

Jog Calibrate
Buttons

LED Status
Lights

Quick-Cal
Switch

Calibration
Switches

Indicator arrow