Flowserve 510si Series Digital Positioner User Manual
Page 4
4
®
User Instructions Logix 510si - LGENIM0510-0
2 12/13
4 SPECIFICATIONS
Table 1: Input Signal
Input Signal Range
4 - 20 mA
Compliance Voltage
6 VDC
Voltage Supply (maximum)
30 VDC
Minimum Required Operating
Current
3,6 mA
Table 2: Stroke Output
Feedback Shaft Rotation
Min. 15°, max 90°
40° recommended for linear
applications
Table 3: Air Supply
Air Supply Quality
Free from moisture, oil and dust
per IEC 770 and ISA-7.0.01
Input Pressure Range
1,5 to 6,0 bar (22 to 87 psi)
Air Consumption (steady state)
0,08 Nm³/h @ 1,5 bar
(0,047 SCFM @ 22 psi)
0,12 Nm³/h @ 6,0 bar
(0,071 SCFM @ 87 psi)
Table 4: Output Signal
Output Pressure Range
0 to 100% of air supply pressure
Output Flow Capacity
2,4 Nm³/h @ 1,5 bar
(1,41 SCFM @ 22 psi)
7,0 Nm³/h @ 6,0 bar
(4,12 SCFM @ 87 psi)
Table 5: Shipping Weights
Base Positioner without
Accessories
1,2 kg (2,65 lbs)
Table 7: Environmental Conditions
Operating Temperature
Standard
-20 °C to +80 °C
(-4 °F to +178 °F)
Operating Temperature
Low
-40 °C to +80 °C
(-40 °F to +178 °F)
Transport and Storage
Temperature
-40 °C to +80 °C
(-40 °F to +178 °F)
Operating Humidity
0 to 100% non-condensing
Table 6: Performance Characteristics (typical)
Linearity
< +/- 1,0%
Resolution
< 0,3%
Repeatability
< 0,5%
Deadband
< 0,5%
Table 9: Limit Switches (optional)
Type
P&F SJ2-S1N
Load current
< 1 mA < 3 mA
Voltage range
5 - 25 VDC
Hysteresis
0,2 %
Temperature
-25 °C to 100 °C (-13 °F to 212 °F)
Type
P&F SJ2-SN
Load current
< 1 mA < 3 mA
Voltage range
5 - 25 VDC
Hysteresis
0,2 %
Temperature
-40 °C to 100 °C (-40 °F to 212 °F)
Type
P&F SJ2-N
Load current
< 1 mA < 3 mA
Voltage range
5 - 25 VDC
Hysteresis
0,2 %
Temperature
-25 °C to 100 °C (-13 °F to 212 °F)
3
LOGIX 510si OVERVIEW
The Logix 510si is a two-wire, 4-20 mA input digital valve
positioner. The Logix 510si positioner controls single-
acting actuators with linear and rotary mountings. The
Logix 510si is completely powered by the 4-20 mA input
signal. The minimum input signal required to function
is 3,6 mA.
Since the positioner is insensitive to supply pressure
changes and can handle supply pressures from 1,5 to
6 barg (22 to 87 psig), a supply regulator is usually not
required; however, in applications where the supply pres-
sure is higher than the maximum actuator pressure rating
a supply regulator is required to lower the pressure to
the actuator’s maximum rating (not to be confused with
operating range). A coalescing air filter is recommended
Table 8: Hazardous Area Specifications
ATEX
II1G Ex ia IIC T4 - T6
II3G Ex ic IIC T4 - T6
FM
Class I, Division 2, Groups A,B,C,D Temp. Class. T4 Ta = 85°C
Class I Zone = Group IIC T4 Ta = 85°C
Class I, Division 2, Groups A,B,C,D Temp. Class. T4 Ta = 85°C
CSA
Class I Division 1, Groups A,B,C,D
Class I Division 2, Groups A,B,C,D