THERMOSTAT WIRING

AIR LOUVER ADJUSTMENTS

SYSTEM START-UP

1) Mounting location of thermostat should be on an interior wall

approximately 4-5 feet above the floor, which will not be

subjected to drafts and is not in the direct path of the

discharge airstream of the unit.

2) Make sure 5/8" snap bushing has been installed in 5/8"

knockout on cabinet wrapper to protect low voltage wiring.

Route thermostat wire through bushing and raceway to the

low voltage junction box.

3) Wire low voltage circuit as indicted on unit wiring diagram.

For units without electric heat option, do not connect thermo-

stat wiring to "W" terminal at thermostat or to "W" lead (white)

at low voltage junction box.

The discharge air louvers may be adjusted in one or several

positions to direct airflow to one or more areas of the room.

To adjust, pull louver straight out from recessed position and

rotate louver to desired direction then reinsert into recessed

position.

Note: Do not pull louver out further than required during

adjustment for spring may become stretched.

1) Prior to start-up, inspect the blower to assure the wheels turn

freely without rubbing on the housing.

2) This fan coil is equipped with a 3-speed motor which gives

the consumer the option of High-Med or Med-Low fan

speeds. The unit is factory set at High-Med, however if

installation requires a quieter application, remove blower/

motor wiring plug and insert into lower socket for Med-Low

speeds.

Note: If unit has electric heat, refer to wiring diagram on

unit for proper fan speed combination.

WARNING: All panels must be installed before operat-

ing unit.

3)

System check

- set thermostat system switch to "Off"

position and fan switch to "Auto" position. Apply power to

both the indoor and outdoor units.

4) Set fan switch to "On", fan should operate.

5) Return fan switch to "Auto" position. Set system switch to

"Cool" and lower thermostat set point to coldest setting.

Outdoor unit should energize as well as fan coil.

6) Set system switch to "Heat" and raise thermostat to a set

point warmer than room temperature. Outdoor unit should

energize as well as fan coil. If unit has electric heat, raise

thermostat to the warmest set point, within a minute the

electric heat should energize.

7) Return system switch to off position.

The only maintenance required to be performed is to keep the

air filter clean. Allowing dust to form on the filter will eventually

cause the unit to loose efficiency. Once a month check and

clean filter if required.

The filter is a permanent type and may be removed and

washed with a garden hose. Filter should be completely dry

before reinstalling.

MAINTENANCE