beautypg.com

Condensate drain line, Electrical, Refrigerant piping – First Co DFCH Ductless Fan Coil Upflow / Horizontal Heat Pump or DX - 1.5 to 2.5 tons User Manual

Page 3: Refrigerant charging

background image

CONDENSATE DRAIN LINE

2) Install a rigid (copper) drain line connected to the drain pan

nipple (5/8" OD) and extending out the rear of the cabinet.

This line must be sloping down slightly from the drain pan to

the rear of the cabinet.

3) The rigid drain line should drain directly outdoors or connect

to an open drain trap. An open drain trap is required to

prevent any possible sewer gas from entering the fan coil unit

through the drain line.

It is also necessary to have adequate slope in the drain line

from the fan coil unit to the open trap or outdoors to ensure

proper drainage.

Warning: The condensate pan will overflow if drain line

is higher than drain pan at any point.

4) A condensate pump must be installed if the drain line is to be

run above the drain pan elevation. The pump must be

located external to the fan coil unit and lower than the drain

pan in order to operate properly. (See condensate pump

installation instructions.)

Drain line installation must adhere to all code requirements.

Wall or Floor Mount (Vertical)

Figure 1 shows the location of the condensate knockouts.

Install a rigid (copper) drain line connected to the drain pan

nipple (5/8" OD). The condensate line should drain directly

outdoors or connect to an open drain trap. An open drain trap

is required to prevent any possible sewer gas from entering the

fan coil unit through the drain tube.

It is also necessary to have adequate slope in the drain line

from the fan coil unit to the open trap or outdoors to ensure

proper drainage.

Ceiling Mount (Horizontal)

Figure 2 shows the location of the condensate knockouts.

The following requirements should be met to insure proper

drainage of condensate from the pan in the horizontal position:

1) Fan coil must be installed level.

ELECTRICAL

All wiring must comply with local and national code require-

ments. Units are provided with wiring diagrams, located on

electrical compartment panel, and nameplate data to provide

information required for necessary field wiring. A 7/8" AND 1-1/

8" knockout is provided as entry points for field wiring. Refer to

figure 1 and 2. If 1-1/8" knockout is used install snap bushing in

hole and route flex conduit through snap bushing to 7/8" hole in

electrical box and secure.

These units are provided with a Class 2 transformer for 24-volt

control circuits. Should any add-on equipment used also have

a Class 2 transformer furnished, care must be taken to prevent

interconnecting outputs of the two transformers by using a

thermostat with isolating contacts.

REFRIGERANT PIPING

Upon completion of refrigerant connections check all connec-

tions for leaks. In addition the suction line must be fully insulated

to prevent sweating of refrigerant line within the unit. A length of

Armaflex insulating tape has been shipped with the unit for this

propose.

Reinstall drain pan to original position.

Entry points for the refrigerant lines are shown in Figure 1 and

2. These lines must be sized in accordance with the outdoor unit

manufacturer’s recommendations. The evaporator coil is fac-

tory supplied for sweat connections on the liquid and suction

lines. A short preformed 90 degree copper elbow is also factory

supplied to facilitate the connection to the suction line at the

evaporator.

To ease the installation of the refrigerant lines to the evapora-

tor, remove the drain pan by sliding it out of the fan coil unit.

REFRIGERANT CHARGING

Refer to outdoor manufacturer installation instructions for initial

charging instructions. Even though the outdoor unit is factory

precharged, the charge must be checked and adjusted if re-

quired.

Allow sufficient running time in the cooling cycle, 20 to 30

minutes, for system to balance. At this time you must check the

sub-cooling of the liquid refrigerant at the outdoor unit to insure

a proper liquid seal is present at the expansion valve.

At outdoor conditions between 80 to 95 degrees the system

should be charged to a sub-cooling level of 8 to 10 degrees at

the outdoor unit. This charge will permit the expansion valve to

operate properly at a superheat level of 6 to 8 degrees. Super-

heat at the outdoor unit will be in the range of 12 to 18 degrees.

To increase sub-cooling increase refrigerant charge.

To decrease sub-cooling decrease refrigerant charge.