Planning the location of the post barbecue, Installation – Fire Magic Deluxe Post Barbecue Patio Mount User Manual
Page 6

6
PLANNING THE LOCATION OF THE POST BARBECUE
This barbecue is designed FOR OUTDOOR USE ONLY.
DO NOT use this unit under overhead combustible construction. DO NOT use this appliance inside a building, garage, or
any unprotected, enclosed area (see EXHAUST REMOVAL). It must not be used in or on recreational vehicles or boats.
Important:
This unit is NOT insulated and therefore during use it must be located with a minimum of 18" of side and back
clearance from unprotected combustible materials such as wood, plastic, or stucco with wood framing.
INSTALLATION
GAS SUPPLY PLUMBING REQUIREMENTS
For natural gas or a household propane system, rigid
1/2", or 3/4" black steel pipe, or local code approved
pipe is required to conduct the gas supply to the
unit. An outdoor approved fl exible connector can be
used to connect your household gas supply to the
barbecue. DO NOT use a rubber hose within the
grill enclosure. Apply only joint compounds that
are resistant to all gasses on all male pipe fi ttings.
Note: If 1/2" pipe is used with natural gas, it
should be no longer than 20'.
Important: An external valve (with a removable
key) in the gas line is necessary for
safety when the barbecue is not in
use. It also provides for convenient
maintenance.
GAS SUPPLY AND MANIFOLD PRESSURES
For natural gas - Normal 7" water column (w.c.),
minimum 5" w.c., maximum 10 1/2" w.c.
For propane gas - Normal 11" w.c., minimum 8"
w.c., maximum 13" w.c.
ENSURING PROPER COMBUSTION AIR AND
COOLING AIR FLOW
You must maintain proper air fl ow for the barbecue
to perform as it was designed (Fig.
6-1
). If airfl ow
is blocked, overheating
and poor combustion
will result. Do not block
the 1" front air inlet along
the bottom of the face or
more than 75% of the
cooking grid surface with
objects such as pans or
griddles.
Note: The 1" front air space allows access to the
drip tray.
ELECTRICAL OUTLETS
All electrical outlets in the vicinity of the barbecue
must be properly grounded.
Note: Keep electrical supply cords away from all
heated surfaces.
EXHAUST REMOVAL
If installed or used under a patio roof, the cooking
grid area must be fully covered by a chimney and
exhaust hood. An exhaust fan with a rating of
1,000 CFM (cubic feet per minute) or more may be
necessary to effi ciently remove smoke and other
cooking by-products from the covered area. This
barbecue shall not be used under unprotected
overhead combustible construction. THIS UNIT
SHOULD NOT BE LOCATED IN A FULLY
ENCLOSED AREA OF ANY KIND.
CAUTION: Wind blowing into or across the rear
oven lid vent (Fig. 6-2) can cause
poor performance and/or dangerous
overheating. Orient the grill so that
the prevailing wind blows toward the
front of the grill (Fig. 6-3).
CAUTION: To prevent dangerous overheating,
the rear of the unit must have a
minimum clearance of 4” from any
backsplash/wall.
Fig. 6-3
PLACE GRILL SO PREVAILING WIND
BLOWS TOWARD FRONT OF GRILL
YOU MUST PROTECT REAR OVEN
VENT FROM PREVAILING WIND
Fig. 6-2
Fig.
6-1
Ventilation Diagram
CORRECT
Rear oven lid vent
INCORRECT
YOU
YOU MU
MUST
ST PRO
PROTEC
TECT R
T REAR
EAR OV
OVEN
EN