beautypg.com

Inputs and outputs, Model iboot-io 1410037, Model iboot-io-off 1410039 – Dataprobe iBoot-IO User Manual

Page 2: Dry contact versions - specifications

background image

V150212E

iBoot-IO

Page 2

2.2. Inputs and Outputs

The screw terminal blocks are on removable connectors for easy cable fabrication. Follow the correct
diagram and table co-responding to the proper model.

Make sure screw terminals are tightened securely and that there are no loose strands of cable, or excessive
stripped wires.

2.3. Model iBoot-IO 1410037

Default Power ON

Dry Contact Control

iBoot-IO

Function

O Feedback Output

High(Open) = Power OFF
Low (Ground) = Power ON

G Ground

Common Ground

I

Control Input

Open = Power ON
Ground= Power OFF

2.4. Model iBoot-IO-OFF 1410039

Default Power OFF

Dry Contact Control

iBoot-IO-OFF

Function

O Feedback Output

High(Open) = Power OFF,
Low (Ground) = Power ON

G Ground

Common Ground

I

Control Input

Open = Power OFF
Ground= Power ON

2.5. Dry Contact Versions - Specifications

Input Relay Coil Sensitivity:

44mA @ 12 VDC

Output Transistor Rating:

100 mA 30 VDC Max.

Poor Screw Terminal

Connections.

Note Loose Wires and

Excessive Stripping

Proper Screw Terminal

Connections

Wiring Diagram for Dry Contact Versions

iBoot-IO and iBoot-IO-OFF