Contemporary Control Systems BACnet Cube I/O BMT-AI8 User Manual
Page 3
![background image](https://www.manualsdir.com/files/779099/content/doc003.png)
10. Software Description
Device Object
Property
Remark / Value
RW
Object_Identifier
device, default instance: 421000 + Network-Address
RW-E
Object_Name
max. 63 Bytes,
default “BMT-AI8_” + Network-Address (Hexadecimal)
RW-E
Object_Type
DEVICE (8)
R
System_Status
OPERATIONAL (0)
R
Vendor_Name
“BTR Netcom GmbH”
R
Vendor_Identifier
421
R
Model_Name
“BMT-AI8”
R
Description
max. 127 Bytes, default “”
RW-E
Location
max. 63 Bytes, default “”
RW-E
Firmware_Revision
“1.2”
R
Application_Software_Version
“1”
R
Protocol_Version
1
R
Protocol_Revision
12
R
Protocol_Services_Supported
read-property, write-property, subscribe-cov, who-has, who-is,
device-communication-control, reinitialize-device
R
Protocol_Object_Types_Supported
DEVICE, ANALOG_INPUT, ANALOG_VALUE,
MULTISTATE_VALUE, GROUP
R
Object_List [49]
device, analog-input 1…8, analog-value 1…28,
multistate-value 1…9, group 1…3
R
Max_APDU_Length_Accepted
480
R
Segmentation_Supported
NO_SEGMENTATION (3)
R
APDU_Timeout
10000
R
Number_Of_APDU_Retries
3
R
Device_Address_Binding
-
R
Database_Revision
0
R
Max_Master
0…127, default 127
RW-E
Max_Info_Frames
1…255, default 1
RW-E
Active_COV_Subscriptions
max. 10 Subscriptions, for analog-input 1…8,
Confirmed / Unconfirmed, Lifetime = 0…65535 sec.
R
R: Read Property, W: Write Property, -E: Storage in EEPROM / Flash
Analog Input Object 1…8
Property
Remark / Value
RW
Object_Identifier
analog-input, instance 1 … 8
R
Object_Type
ANALOG_INPUT (0)
R
Object_Name
max. 42 Bytes, default “Input 1” … “Input 8”
RW-E
Description
max. 84 Bytes, default “”
RW-E
Present_Value
Measured value,
writable if Out_Of_Service,
Measurement Range defined in Multistate Value 1…8
R
RW
Status_Flags
IN_ALARM: 0
FAULT: 0
OVERRIDDEN: 0
OUT_OF_SERVICE:
0 / 1
R
Event_State
NORMAL (0)
R
Out_Of_Service
FALSE (0) / TRUE (1)
RW
Units
Defined in Multistate Value 1…8
R
COV_Increment
Minimum change of Present_Value for COV notification,
default 1.0
RW-E
Notification_Class
Unsubscribed UnconfirmedCOVNotification
0: no COV notification, default,
1: local broadcast,
2: global broadcast
RW-E
R: Read Property, W: Write Property, -E: Storage in EEPROM / Flash
Continuation Software Description
Analog Value Object 21…28
Property
Remark / Value
RW
Object_Identifier
analog-value, instance 21 … 28
R
Object_Type
ANALOG_VALUE (2)
R
Object_Name
max. 42 Bytes, default “Offset 1” … “Offset 8”
RW-E
Description
max. 84 Bytes, default “”
RW-E
Present_Value
Offset is added to measured value (Analog Input 1 … 8),
default 0.0
RW-E
Status_Flags
IN_ALARM: 0
FAULT: 0
OVERRIDDEN: 0
OUT_OF_SERVICE: 0
R
Event_State
NORMAL (0)
R
Out_Of_Service
FALSE (0)
R
Units
same as Analog Input 1 … 8
R
R: Read Property, W: Write Property, -E: Storage in EEPROM / Flash
Multistate Value Object 1…8
Property
Remark / Value
RW
Object_Identifier
multistate-value, instance 1 … 8
R
Object_Type
MULTISTATE_VALUE (19)
R
Object_Name
max. 42 Bytes,
default “Measurement Range 1” … “Measurement Range 8”
RW-E
Description
max. 84 Bytes, default “”
RW-E
Present_Value
Measurement Range of Analog Input 1…8
Voltage (%, Volt)
Voltage, Pullup Resistor 2kOhm to 5V (% P, Volt P)
Resistance (Ohm)
User defined Sensor
Standard Temperature Sensors
RW-E
Status_Flags
IN_ALARM: 0
FAULT: 0
OVERRIDDEN: 0
OUT_OF_SERVICE: 0
R
Event_State
NORMAL (0)
R
Out_Of_Service
FALSE (0)
R
Number_Of_States
19
R
State_Text
max. 20 Bytes, default see next Table
RW-E
R: Read Property, W: Write Property, -E: Storage in EEPROM / Flash
METZ CONNECT GmbH
Im Tal 2 | 78176 Blumberg | Germany | Phone +49 7702 533-0 | Fax +49 7702 533-433
Mounting instruction see www.metz-connect.com