background image

TD675300-0ID

5

Connecting Cables

Each AI-FR hub provides fiber ring continuity with either a coaxial bus
(/CXB) or twisted-pair bus (/TB5) local drop.

Connecting the Fiber Optic Cable

Bayonet-locking-style ST connectors (mechanically similar to BNC coaxial
cable connectors) are provided for attaching fiber optic cable (typically
multimode) of 50/125, 62.5/125, or 100/140 in size.

Connecting Coaxial Cable Bus Networks (-CXB)

The AI-FR/CXB allows RG-62/u coaxial cabling to various nodes via BNC
“T” connectors at each device. Each end of a segment must be terminated
with 93 ohms of passive resistance using a BNC terminator (BNC-TER). If
the AI-FR occupies one end of the bus, it also must have the added
termination. Make sure that all devices are -CXB compliant.

Connecting Shielded Twisted-Pair Bus Networks (-TB5)

The AI-FR/TB5 has dual RJ-45 connectors for communication with various
nodes via shielded twisted-pair cable. Each end of a segment must be
terminated with 100 ohms of passive resistance using a TB5 terminator
(TB5-TER). If the AI-FR occupies one end of the bus, it also must have the
added termination.

Determining Maximum Ring Length for the AI-FR/TB5

11.9

µ

s – (Number of Hubs

330 ns)

Formula:

Max Ring Length =

5 ns

Table:

Max Ring Length versus Hub Count

Number of

Max Ring

Hubs

Length

2

2248

3

2182

4

2116

5

2050

6

1984

7

1918

8

1852

9

1786

10

1720