6

DIAGNOSTICS

6.1

E

THER

CAT

STATUS INDICATOR

Bronkhorst instruments contain an EtherCAT two color status led: green and red. The led indicates the actual

EtherCAT run state (green) and the actual error state (red).

The status led has several indicator states, which are applicable for both green and red. They are described in the

table below.

Indicator state

Definition

on

The indicator is constantly on

off

The indicator is constantly off

blinking

The indicator is repeatedly on for 200 ms and off for 200 ms

single flash

The indicator is repeatedly on for 200 ms and off for 1000 ms

double flash

The indicator shows repeatedly a sequence of two short flashes (200

ms), separated by an off phase (200 ms), followed by a long off phase

(1000 ms)

6.1.1

Run indicator

EtherCAT state

Indicator state (green)

Init

off

Pre-Operational

blinking

Safe-Operational

single flash

Operational

on

6.1.2

Error indicator

Error state

Indicator state (red)

No error

off

invalid state change commanded by master (e.g. from

Init to Operational)

request for state change to an unsupported state (e.g.

Bootstrap)

request for state change to an unknown state

blinking

invalid mailbox configuration

invalid SyncManager configuration

single flash

Application watchdog timeout (e.g. when EtherCAT

communication cable is removed)

double flash