Burner adjustments – Boyertown Solaia CSL6230 - CSL12590 Cast Iron Boiler User Manual
Page 21

21
Burner Adjustments
Warning: Before proceeding read and fully understand the instructions contained in the
burner manual.
Failure to comply can result in an explosion causing extensive property damage, severe personal
injury, or death.
Preliminary Oil Burner Settings
Boiler Burner
Nozzle
Pump
Press
CO
2
Smoke
CSL6230
Riello F10
2.00 x 60B
150 PSI
11.0%
#0
CSL7290
Riello F15
2.25 x 60B
175 PSI
11.0%
#0
CSL8350
Riello F15
2.50 x 60B
175 PSI
11.0%
#0
CSL9410
Riello F15
3.00 x 60B
175 PSI
11.0%
#0
CSL10470
Riello F15
3.50 x 60B
175 PSI
11.0%
#0
CSL11530
Riello F20
4.00 x 60B
175 PSI
11.0%
#0
CSL12590
Riello F20
4.50 x 60B
175 PSI
11.0%
#0
Preliminary Gas Burner Settings
Boiler Burner
Gas
Type
Input
Btu/Hr
Gas Inlet
Size
Manifold
Pressure
Head
Air
Setting
CO
2
Nat 322,000 1”
2.40”
3
7.75
9.0%
CSL6230 HeatWise
SU-3
LP 322,000 1”
1.90” 3
8.25 11.0%
Nat
406,000 1” 3.10” 7 14.25 9.0%
CSL7290 HeatWise
SU-4
LP 406,000 1”
2.50” 7
14.5 11.0%
Nat 490,000 1”
3.40” 20
20
9.0%
CSL8350 HeatWise
SU-4
LP 490,000 1”
2.30” 20 18.5 11.0%
Nat 574,000 1”
2.10” 2”
7.5
9.0%
CSL9410 HeatWise
SU-5
LP 574,000 1”
1.55” 2”
7.5
11.0%
Nat 658,000 1”
2.70” 2”
8.7
9.0%
CSL10470 HeatWise
SU-5
LP 658,000 1”
2.05” 2”
8.7
11.0%
Nat 742,000 1-1/4” 1.13” 2-5/8” 4.25
9.0%
CSL11530 HeatWise
SU-6
LP 742,000 1-1/4” 0.76” 2-5/8” 4.75 11.0%
Nat 826,000 1-1/4” 1.40” 2-5/8” 4.75
9.0%
CSL12590 HeatWise
SU-6
LP 826,000 1-1/4” 0.95” 2-5/8” 5.1
11.0%
Control Circuit Safety Checks
Check the safety controls on the boiler after completing the oil burner adjustments. A safety control check
for satisfactory performance must be performed.
1. High limit control - Remove the temperature control cover as needed and note temperature setting.
With the burner running, reduce the high limit setting until the burner shuts off. Return the high limit to
its original setting.
2. Auxiliary high limit control - Remove the temperature control cover as needed and note temperature
setting. With the burner running, reduce the high limit setting until the burner shuts off. Return the
high limit to its original setting.
3. Primary control and flame sensors – Refer to the oil or gas burner manual supplied with the burner.
4. Low Water cutoff - Follow manufacturers recommendations for testing of the low water cut off.