beautypg.com

Burner adjustments – Boyertown Solaia CSL6230 - CSL12590 Cast Iron Boiler User Manual

Page 21

background image

21

Burner Adjustments

Warning: Before proceeding read and fully understand the instructions contained in the
burner manual.

Failure to comply can result in an explosion causing extensive property damage, severe personal
injury, or death.

Preliminary Oil Burner Settings


Boiler Burner

Nozzle

Pump

Press

CO

2

Smoke

CSL6230

Riello F10

2.00 x 60B

150 PSI

11.0%

#0

CSL7290

Riello F15

2.25 x 60B

175 PSI

11.0%

#0

CSL8350

Riello F15

2.50 x 60B

175 PSI

11.0%

#0

CSL9410

Riello F15

3.00 x 60B

175 PSI

11.0%

#0

CSL10470

Riello F15

3.50 x 60B

175 PSI

11.0%

#0

CSL11530

Riello F20

4.00 x 60B

175 PSI

11.0%

#0

CSL12590

Riello F20

4.50 x 60B

175 PSI

11.0%

#0

Preliminary Gas Burner Settings

Boiler Burner

Gas

Type

Input

Btu/Hr

Gas Inlet

Size

Manifold
Pressure

Head

Air

Setting

CO

2

Nat 322,000 1”

2.40”

3

7.75

9.0%

CSL6230 HeatWise

SU-3

LP 322,000 1”

1.90” 3

8.25 11.0%

Nat

406,000 1” 3.10” 7 14.25 9.0%

CSL7290 HeatWise

SU-4

LP 406,000 1”

2.50” 7

14.5 11.0%

Nat 490,000 1”

3.40” 20

20

9.0%

CSL8350 HeatWise

SU-4

LP 490,000 1”

2.30” 20 18.5 11.0%

Nat 574,000 1”

2.10” 2”

7.5

9.0%

CSL9410 HeatWise

SU-5

LP 574,000 1”

1.55” 2”

7.5

11.0%

Nat 658,000 1”

2.70” 2”

8.7

9.0%

CSL10470 HeatWise

SU-5

LP 658,000 1”

2.05” 2”

8.7

11.0%

Nat 742,000 1-1/4” 1.13” 2-5/8” 4.25

9.0%

CSL11530 HeatWise

SU-6

LP 742,000 1-1/4” 0.76” 2-5/8” 4.75 11.0%
Nat 826,000 1-1/4” 1.40” 2-5/8” 4.75

9.0%

CSL12590 HeatWise

SU-6

LP 826,000 1-1/4” 0.95” 2-5/8” 5.1

11.0%

Control Circuit Safety Checks

Check the safety controls on the boiler after completing the oil burner adjustments. A safety control check
for satisfactory performance must be performed.

1. High limit control - Remove the temperature control cover as needed and note temperature setting.

With the burner running, reduce the high limit setting until the burner shuts off. Return the high limit to
its original setting.

2. Auxiliary high limit control - Remove the temperature control cover as needed and note temperature

setting. With the burner running, reduce the high limit setting until the burner shuts off. Return the
high limit to its original setting.

3. Primary control and flame sensors – Refer to the oil or gas burner manual supplied with the burner.
4. Low Water cutoff - Follow manufacturers recommendations for testing of the low water cut off.