Venting, Name plate installation, Aquastat installation and adjustment – Boyertown Solaia CSL6230 - CSL12590 Cast Iron Boiler User Manual
Page 15: Chimney
15
Figure 7
Name Plate Installation
Install nameplate provided in the upper left jacket corner. Transfer the boiler serial number which is rivited
to the front leg of the boiler to the nameplate.
Aquastat Installation and Adjustment
1. After cabinet installation is complete install the temperature control on the right side of the boiler.
Attach the aquastat to the jacket side panel using sheet metal screws and the holes provided in the jacket
panel. The sensor wires should be run through the bottom knockout in the aquastat. The rubber
grommet provided with the sensor wires is to be securely inserted into the aquastat knockout.
2. Connect the sensor leads to the appropriate temperature control terminals.
3. Connect your line voltage and thermostat wires if applicable to the control. See electrical diagrams for
proper connections.
4. Honeywell L7248 - The overall range of the High Limit is from 130
0
F to 220
0
F. Typically it would be
set in the range of 180
0
F to 200
0
F.
VENTING
Warning: The vent installation must be in accordance with the National Fuel Gas Code
ANSI Z223.1/NFPA 54, the ASHRAE Equipment Handbook on Venting or the applicable
provisions of local building codes. Failure to follow all instructions can result in flue gas spillage
and carbon monoxide emissions, causing severe personal injury or death.
Chimney
The boiler must be connected to an adequate chimney or an approved venting system in accordance with
these instructions. An adequate chimney or venting system is one that is sealed and lined with the capability
of producing a -.04" W.C. flue draft and having the capacity to handle the amount of flue gas that is
introduced. A chimney with an internal construction of corrosion resistant tile, stainless steel, or some other
material that will withstand flue gas temperatures up to 1000
0
F is required.