FC510x: Bus Node Diagnostics
The CANopen fieldbus card FC510x has a comprehensive range of diagnostic options for connected network 
nodes. 
For each CANopen fieldbus node there is a node state input variable, which signals the status of the current 
slave during the runtime and can be linked, for example with the PLC. 
Node State (Box-State)
Node 
State 
Meaning
Explanation
0 = 0x00
No error
Bus node is operational, communication is running correctly
1 = 0x01
Node deactivated The node is subject to one or more of the following errors:
- guarding/heartbeat error (failure, toggle bit error, node has changed state) 
- expected TxPDO has not been received 
- TxPDO length shorter than expected 
Node has been stopped, because "Manual restart" following a node failure 
has been selected. 
2 = 0x02
Node not found
Node not found: no answer to SDO read access to object 0x1000 at the 
expected node address. Check the following at the node: what node address 
is set, and what baud rate. Check network (terminating resistors, connectors, 
bus length, crossed wiring etc.) 
4 = 0x04
SDO syntax error 
at StartUp 
Error during SDO write access: SDO abort by node. See the "Diag" tab for 
details. 
or: the length of an object read by SDO does not agree with the expected 
length. 
5 = 0x05
SDO data mis-
Expected data does not agree with that read via SDO (e.g. device profile