Software-reset, Fibre-optic fracture point test, Invalid function selection – BECKHOFF C1220 User Manual
Page 15
Eiserstraße 5 / D-33415 Verl / Telefon 05246/963-0 / Telefax 05246/963-149
15
Software description of functions
Beckhoff Lightbus - PC interface card C1220
Software-RESET
The C1220 can be reset by means of this function. Besides reinitialization
of the fibre-optic ring, the controller and the dual ported RAM are also
reinitialized. Completion of RESET is acknowledged by the code word
(without Data Valid).
Argument
Channel
Length
Function
0
1
2
Comment
Request
02
0x09
Reply
04
0x02
fe
af
Fibre-optic fracture point test
A fracture point in the fibre-optic ring can be localized by this function.
Depending on the result, the test specifies the number of boxes in the ring
or the location of the fracture point.
Argument
Channel
Length
Function
0
1
2
Comment
Request
02
0x0a
Reply
04
0x0a
00
nn
No fracture point,
nn modules in the ring
04
0x0a
01
nn
Fracture point before nn th-module before
the receiver input of the C1220
04
0x0a
01
ff
Fracture point cannot be located (fracture
point before receiver input)
If the fracture point should be specified as not being capable of location, it
is probably located between the last module and the receive input of the
C1220.
Invalid function selection
If a function is requested via handshake channel 0 that is reserved or is not
available, it is acknowledged with the function 0x0ff, which contains the
invalid function number as Argument 0.
Example:
Argument
Channel
Length
Function
0
1
2
Comment
Request
03
0x04
01
Request function 4
(reserved)
Reply
03
0x0ff
04