4 technical data, 1 permissible ambient and operating conditions – BECKHOFF AX5000 60 A - 170 A User Manual
Page 17

BECKHOFF
Drive Technology
4 Product description
AX5000
Version: 1.4
17
4.4
Technical data
UL-Listing!
It is essential to observe chapter 3.3 if you wish to operate an AX5000 in an
economic area that requires a UL-Listing.
4.4.1
Permissible ambient and operating conditions
Ambient / operating conditions
Permissible values
Ambient temperature during operation 0 °C up to +40 °C
Up to 55 °C with reduced power (2 % / °C)
Ambient temperature during transport -25 °C up to +70 °C
Ambient temperature during storage
-25 °C up to +55 °C
Air humidity
15 % up to 85 %, non-condensing
Pollution degree
2 according to EN 60664-1
Corrosion protection
Normally not required.
Under extreme operating conditions separate
measures must be agreed with the manufacturer.
Operating altitude
up to 1000 m above sea level without reduced power.
Between 1000 m and max. 2000 m with reduced
power 1 % per 100 m.
Installation position
vertical
Ventilation
Built-in temperature-controlled fan
Protection class
IP 20 except the terminals (IP00)
EMC
Category C3 - standard
Category C2, C1 - auxiliary filter required