Safe parameters overview
Parameter name
Meaning
Values
FSoE_Address
Address of the rotary switch or the setting
in the EP1908
1 to 4095
Operating Mode
Digital
Digital
Sensor test channel 1
active
The clock signal of channel 1 (pin 1) is
checked at the channel 1 input (pin 2).
TRUE / FALSE
Sensor test channel 2
active
The clock signal of channel 2 (pin 3) is
checked at the channel 2 input (pin 4).
TRUE / FALSE
Sensor test channel 3
active
The clock signal of channel 3 (pin 3) is
checked at the channel 1 input (pin 2).
TRUE / FALSE
Sensor test channel 4
active
The clock signal of channel 4 (pin 3) is
checked at the channel 4 input (pin 4).
TRUE / FALSE
Sensor test channel 5
active
The clock signal of channel 5 (pin 5) is
checked at the channel 1 input (pin 2).
TRUE / FALSE
Sensor test channel 6
active
The clock signal of channel 6 (pin 3) is
checked at the channel 6 input (pin 4).
TRUE / FALSE
Sensor test channel 7
active
The clock signal of channel 7 (pin 7) is
checked at the channel 1 input (pin 2).
TRUE / FALSE
Sensor test channel 8
active
The clock signal of channel 8 (pin 3) is
checked at the channel 8 input (pin 4).
TRUE / FALSE
Logic channel 1 and 2
Logic of channels 1 and 2
see operating modes table
Logic channel 3 and 4
Logic of channels 3 and 4
see operating modes table
Logic channel 5 and 6
Logic of channels 5 and 6
see operating modes table
Logic channel 7 and 8
Logic of channels 7 and 8
see operating modes table
Velocity limit channel 1
Upper frequency limit for channel 1
Frequency in 1/10 Hz
Velocity limit channel 2
Upper frequency limit for channel 2
Frequency in 1/10 Hz
Velocity limit channel 3
Upper frequency limit for channel 3
Frequency in 1/10 Hz
Velocity limit channel 4
Upper frequency limit for channel 4
Frequency in 1/10 Hz
Velocity limit channel 5
Upper frequency limit for channel 5
Frequency in 1/10 Hz
Velocity limit channel 6
Upper frequency limit for channel 6
Frequency in 1/10 Hz
Velocity limit channel 7
Upper frequency limit for channel 7
Frequency in 1/10 Hz
Velocity limit channel 8
Upper frequency limit for channel 8
Frequency in 1/10 Hz
Store Code
This parameter is required for the
TwinSAFE Restore Mode
0x0000
Project CRC
This parameter is required for the
TwinSAFE Restore Mode
0x0000
Identity
internal use (read only)
Detected Modules
internal use (read only)