3 technical data – BECKHOFF EP1908 User Manual
Page 11

Product description
EP1908-0002
9
3.3 Technical data
Product designation
EP1908-0002
Fieldbus
EtherCAT
Number of inputs
8
Connecting the inputs
M12
Status display
8 (one green LED per input)
Reaction time
(Read input/write to E-bus)
typically: 4 ms,
maximally: see error reaction time
Watchdog time
adjustable from 2 ms to 60 s
Error reaction time
≤
watchdog time
Frequency range for speed measurement
2 Hz to 500 Hz
Cable length between
sensor and EtherCAT Box
(unshielded)
30 m max.(at 0.75 or 1 mm²)
(shielded)
30 m max.(at 0.75 or 1 mm²)
Output current of the clock outputs
typically 10 mA, max. 15 mA
Input process image
6 byte
Output process image
6 byte
Supply voltage for the EP1908
24 V
DC
(-15%/+20%)
Power consumption Us
(connected with eight potential-free contacts)
8 channels occupied: typically 87 mA
0 channels occupied: typically 80 mA
Current consumption U
P
(connected with eight potential-free contacts)
8 channels occupied: approx. 27 mA
0 channels occupied: approx. 6 mA
Power dissipation of the EtherCAT Box
typically 3 watts
Electrical isolation (between the channels)
no
Electrical isolation (between the channels and
EtherCAT)
yes
Insulation voltage (between the channels and
EtherCAT, under common operating conditions)
insulation tested with 500 V
DC
Dimensions (W x H x D)
30 mm x 126 mm x 26.5 mm
Housing material
PA6-F (polyamide)
Sealing compound
polyurethane
Weight
approx. 170 g
Permissible ambient temperature (operation)
-25
℃
to +70
℃
Permissible ambient temperature
(transport/storage)
-40
℃
to +85 °C
Permissible air humidity
5 % to 95 %, non-condensing
Permissible air pressure
(operation/storage/transport)
750 hPa to 1100 hPa
Impermissible operating conditions
TwinSAFE EtherCAT boxes must not be used under
the following conditions:
•
under the influence of ionizing radiation
•
in corrosive environments
EMC immunity/emission
according to EN 61000-6-2 / EN 61000-6-4
Vibration / shock resistance
according to EN 60068-2-6 / EN 60068-2-27
Shocks
15 g with pulse duration 11 ms in all three axes
Protection class (when screwed together)
IP65, IP66, IP67 (according to EN 60529)
Permissible installation position
Variable
Approvals
CE, TÜV SÜD