Operation

26

KL1904

4.2.5 Entering a TwinSAFE address and parameters in the System Manager

The TwinSAFE address set at the DIP switch must also be entered under the Parameters tab
(S_Address entry).

Parameter overview

PrmName

Meaning

Values

S_Address

DIP switch address

1 to 1023

Channel 1

Activation of channel 1

active/not active

Channel 2

Activation of channel 2

active/not active

Channel 3

Activation of channel 3

active/not active

Channel 4

Activation of channel 4

active/not active

Sensor test channel
1

The clock signal for connection Input1+ is
checked at connection Input1-.

active/not active

Sensor test channel
2

The clock signal for connection Input2+ is
checked at connection Input2-.

active/not active

Sensor test channel
3

The clock signal for connection Input3+ is
checked at connection Input3-.

active/not active

Sensor test channel
4

The clock signal for connection Input4+ is
checked at connection Input4-.

active/not active

Channel 1 and 2

For two-channel evaluation, inputs 1 and 2 must
have the same signal states.

single-channel evaluation /
two-channel evaluation

Channel 3 and 4

For two-channel evaluation, inputs 3 and 4 must
have the same signal states.

single-channel evaluation /
two-channel evaluation

Ambivalence
channel 1 and 2

If active, inputs 1 and 2 must have different signal
states.

not active/active

Ambivalence
channel 3 and 4

If active, inputs 3 and 4 must have different signal
states.

not active/active