BECKHOFF KL1904 User Manual
Page 28

Operation
26
KL1904
4.2.5 Entering a TwinSAFE address and parameters in the System Manager
The TwinSAFE address set at the DIP switch must also be entered under the Parameters tab
(S_Address entry).
Parameter overview
PrmName
Meaning
Values
S_Address
DIP switch address
1 to 1023
Channel 1
Activation of channel 1
active/not active
Channel 2
Activation of channel 2
active/not active
Channel 3
Activation of channel 3
active/not active
Channel 4
Activation of channel 4
active/not active
Sensor test channel
1
The clock signal for connection Input1+ is
checked at connection Input1-.
active/not active
Sensor test channel
2
The clock signal for connection Input2+ is
checked at connection Input2-.
active/not active
Sensor test channel
3
The clock signal for connection Input3+ is
checked at connection Input3-.
active/not active
Sensor test channel
4
The clock signal for connection Input4+ is
checked at connection Input4-.
active/not active
Channel 1 and 2
For two-channel evaluation, inputs 1 and 2 must
have the same signal states.
single-channel evaluation /
two-channel evaluation
Channel 3 and 4
For two-channel evaluation, inputs 3 and 4 must
have the same signal states.
single-channel evaluation /
two-channel evaluation
Ambivalence
channel 1 and 2
If active, inputs 1 and 2 must have different signal
states.
not active/active
Ambivalence
channel 3 and 4
If active, inputs 3 and 4 must have different signal
states.
not active/active