14

KL1904

3.3 Technical data

Product designation

KL1904

Number of inputs

4

Number of outputs

0

Status display

4 (one green LED per input)

Reaction time
(read input/write to K-Bus)

typically: 4 ms,
maximally: see error reaction time

Error reaction time

≤ watchdog time

Cable length between
sensor and terminal

(unshielded)

100 m max.(at 0.75 or 1 mm²)

(shielded)

100 m max.(at 0.75 or 1 mm²)

Input process image

6 bytes

Output process image

6 bytes

KL1904 supply voltage

24 V

DC

(–15% / +20%)

Current consumption of the modular electronics
at 24 V (without current consumption of sensors)

4 channels occupied: typically 12 mA
0 channels occupied: typically 1 mA

Current consumption from K-bus

4 channels occupied: typically 47 mA
0 channels occupied: typically 33 mA

Power dissipation of the terminal

typically 540 mW

Electrical isolation (between the channels)

no

Electrical isolation (between the channels and the
K-Bus)

yes

Insulation voltage (between the channels and the
K-Bus, under common operating conditions)

insulation tested with 500 V

DC

Dimensions (W x H x D)

12mm x 100mm x 68mm

Weight

approx. 50 g

Permissible ambient temperature (operation)

-0°C to +55°C

Permissible ambient temperature
(transport/storage)

-25°C to +70°C

Permissible air humidity

5 % to 95 %, non-condensing

Permissible air pressure
(operation/storage/transport)

750 hPa to 1100 hPa

Climate category according to EN 60721-3-3

3K3

Permissible level of contamination

Contamination level 2
(please see the section on cleaning)

Impermissible operating conditions

TwinSAFE terminals must not be used under the
following operating conditions:

 under the influence of ionizing radiation
 in corrosive environments
 in an environment that leads to

unacceptable soiling of the Bus Terminal

EMC immunity/emission

Conforms to EN 61000-6-2 / EN 61000-6-4

Vibration / shock resistance

Conforms to EN 60068-2-6 / EN 60068-2-27

Shocks

15 g with pulse duration 11 ms in all three axes

Protection class

IP20

Permitted operating environment

control cabinet or terminal box with minimum
protection class IP54 according to IEC 60529

Permissible installation position

Variable

Approvals CE