beautypg.com

4 safety parameters – BECKHOFF KL1904 User Manual

Page 17

background image

Product description

KL1904

15

3.4 Safety parameters

Key figures

KL1904

Lifetime [a]

20

Prooftest Interval [a]

not required

1)

PFH 2.30E-09
%SIL3 2.3%
PFD 1.81E-04
%SIL3 18.1%
MTTFd [a]

>100

DC >99%
Performance level

PL e

Category 4
HFT 1
Element classification

2)

Type

A

1)

Special proof tests are not required during the entire service life of the KL1904 Bus Terminal.

2)

Classification according to IEC 61508-2:2010 (see chapters 7.4.4.1.2 and 7.4.4.1.3)

The KL1904 Bus Terminal can be used for safety-related applications within the meaning of
IEC 61508:2010 up to SIL3 and EN ISO 13849-1 up to PL e (Cat4).