4 safety parameters – BECKHOFF KL1904 User Manual
Page 17

Product description
KL1904
15
3.4 Safety parameters
Key figures
KL1904
Lifetime [a]
20
Prooftest Interval [a]
not required
1)
PFH 2.30E-09
%SIL3 2.3%
PFD 1.81E-04
%SIL3 18.1%
MTTFd [a]
>100
DC >99%
Performance level
PL e
Category 4
HFT 1
Element classification
2)
Type
A
1)
Special proof tests are not required during the entire service life of the KL1904 Bus Terminal.
2)
Classification according to IEC 61508-2:2010 (see chapters 7.4.4.1.2 and 7.4.4.1.3)
The KL1904 Bus Terminal can be used for safety-related applications within the meaning of
IEC 61508:2010 up to SIL3 and EN ISO 13849-1 up to PL e (Cat4).
This manual is related to the following products: