Atex - special conditions – BECKHOFF KL3201 User Manual
Page 8

ATEX - Special conditions
6
KL3201, KL3202 and KL3204
ATEX - Special conditions
Observe the special conditions for the intended use of
Beckhoff fieldbus components in potentially explosive areas (directive 94/9/EU)!
WARNING
• The certified components are to be installed in a suitable housing that guaran-
tees a protection class of at least IP54 in accordance with EN 60529! The envi-
ronmental conditions during use are thereby to be taken into account!
• If the temperatures during rated operation are higher than 70°C at the feed-in
points of cables, lines or pipes, or higher than 80°C at the wire branching
points, then cables must be selected whose temperature data correspond to
the actual measured temperature values!
• Observe the permissible ambient temperature range of 0 - 55°C for the use of
Beckhoff fieldbus components in potentially explosive areas!
• Measures must be taken to protect against the rated operating voltage being
exceeded by more than 40% due to short-term interference voltages!
• The individual terminals may only be unplugged or removed from the Bus
Terminal system if the supply voltage has been switched off or if a non-
explosive atmosphere is ensured!
• The connections of the certified components may only be connected or dis-
connected if the supply voltage has been switched off or if a non-explosive at-
mosphere is ensured!
• The fuses of the KL92xx power feed terminals may only be exchanged if the
supply voltage has been switched off or if a non-explosive atmosphere is en-
sured!
• Address selectors and ID switches may only be adjusted if the supply voltage
has been switched off or if a non-explosive atmosphere is ensured!
Operation of the Bus Terminal System in potentially explosive areas (ATEX)!
Note
Pay also attention to the continuative documentation
Notes about operation of the Bus Terminal System in potentially explosive areas
(ATEX)
that is available in the
download area
of the Beckhoff homepage
http://www.beckhoff.com
!