Register Description
14
KL3201, KL3202 and KL3204
User parameters
R32: Feature register
[0x0106]
The feature register specifies the terminal's operating mode.
Feature bit
no.
Description of the operating mode
Bit 0
1
User scaling (R33, R44) active [0]
Bit 1
1
Manufacturer scaling (R19, R20) active [1]
Bit 2
1
Watchdog timer active [1]
In the delivery state, the watchdog timer is
switched on.
Bit 3
1
Sign / amount representation [0]
Sign / amount representation is active
instead of two's-complement representation
(-1 = 0x8001).
Bit 4
1
Siemens output format [0]
This bit is used for inserting status
information on the lowest 3 bits (see below).
Bit 5.6
-
reserved, do not change
Bit 7
1
Activates filter constant in R37 [0]
Bit 8
1
Over range Protection [1]
If the temperature exceeds 850°C the status
bits are correspondingly set and the output
value is restricted to 850°C.
Bit 9
-
reserved, do not change
Bit 10
1
Two-wire connection [0]
Bit 11
-
reserved, do not change
Bit
15,14,13,12
Element
Valid measuring range
0 0 0 0
PT100
-200°C to 850°C
0 0 0 1
NI100
-60°C to 250°C
0 0 1 0
PT1000
-200°C to 850°C
0 0 1 1
PT500
-200°C to 850°C
0 1 0 0
PT200
-200°C to 850°C
0 1 0 1
NI1000
-200°C to 850°C
0 1 1 0
NI120
-80°C to 320°C
1 1 1 0
Output in Ω
10.0 Ω to 5000.0 Ω
1 1 1 1
Output in Ω
10.0 Ω to 1200.0 Ω
Output format
If only manufacturer scaling via the feature register is active, the output
format is as follows:
1 digit corresponds to 1/10 °C or
1 digit corresponds to 1/10 Ω
If no scaling is active, the output format is as follows:
1 digit corresponds to 1/16 °C or
1 digit corresponds to 1/16 Ω