Technical data
KL3201
KL3202
KL3204
Number of inputs
1
2
4
Power supply
via the K-Bus
Sensor types
PT100, PT200, PT500, PT1000, Ni100, Ni120. Ni1000 resistance
measurement (e.g. potentiometer connection)
Connection
2 or 3-wire (pre-set to 3-wire)
2 wire
Temperature range
-200°C ... +850°C (PT sensors); -60°C ... +250°C (Ni sensors)
Resolution
0.1°C per digit (measuring range 10 to 5000 Ω: 0.5°C per digit)
Electrical isolation
500 V (K-Bus/signal voltage)
Conversion time
~ 200 ms
~ 250 ms
Measuring current
typically 0.5 mA
Meas. error (total meas. range)
< ± 1°C
< ± 1 C (at 0°C ... +55°C)
< ± 1.5 C (at utilization of the extended
temperature range)
Bits width in process image
Input: 1 x 16 bits of
data
(1 x 8 bit
control/status
optional)
Input: 2 x 16 bits of
data
(2 x 8 bit
control/status
optional)
Input: 4 x 16 bits of
data
(4 x 8 bit
control/status
optional)
Current consumption from K-Bus
typically 60 mA
Configuration
no address setting, configuration via bus coupler or controller
Special features
open-circuit recognition
Weight
approx. 70 g
Operating temperature
0°C ... +55°C
-25°C ... +60°C in operation (extended
temperature range)
0°C ... +55°C (according to cULus for
Canada and USA)
0°C ... +55°C (according to ATEX, see
special conditions)
Storage temperature
-25°C ... +85°C
-40°C... +85°C
Relative humidity
95 % no condensation
Vibration / shock resistance
according to EN 60068-2-6 / EN 60068-2-27
EMC resistance burst / ESD
according to EN 61000-6-2 / EN 61000-6-4
Installation position
variable
Protection class
IP20
Approvals
CE, cULus, ATEX