Default values, Module capabilities, Module identification – BECKHOFF BK5000 User Manual
Page 11

Appendix
BK5000
7
Default values
Description
Value range
Default
values
Terminal number
0
Table number
0
Rd/Wr with Software write protection
Register number
0
reserved for ADS
Register number
1
Fieldbus interface
Register content
1.0
PLC Interface
0/1
0
1.1 - 1.2
Send channel of events
0 - 3
0
Register number
2
Terminal bus
0
2.0
Auto reset
0
2.1
Device diagnosis
0
2.2
Map diagnosis data of digital terminals in
process image
1
Register number
3
Process image description
Register conent
3.0
Process image active
0/1
1
3.1
Configuration type
0/1
1
3.2
Complex terminal mapping
0/1
0
3.3
Data format of complex terminals
0/1
0
3.4
Data format digital terminals
0/1
0
3.5
Alignment of complex terminals
0/1
0
3.6
Inputs PI synchronously
0/1
0
3.7
Output PI synchronously
0/1
0
3.8 - 3.9
Reaction on fieldbus error
0,1,2
0
3.10
-
3.11
Reaction on terminal bus error
0,1,2
2
Register number
4,5, 6
--
Register number
7
Offset PLC Interface Master -> Slave
0 - 255
0
Register number
8
Offset PLC Interface Slave ->Master
0 - 255
0
Register number
9
Waiting time after SYNC_0 Command
0 - 65535
200
Register number
10
Waiting time after SYNC_1 Command
0 - 65535
200
Register number
11
Support of all data formats
0/1
0
12
Reserved
13
Comparison mask for digital Diagnosis
2-Bit terminals
0x0002
14
Comparison mask for digital Diagnosis
4-Bit terminals
0x0802
Module Capabilities
LMT class [0]
NMT network class[0 or 2]
DBT class[0 or 2]
NMT node class[0 or 2]
Module Identification
Manufacturer Name:
BKH__
Product Name:
BUSKL__
Serial Number:
00000000000000