Appendix
BK3xxx/LC3100
65
Programmed configuration
Index
Description
0
OV-Header
5
Data type Unsigned8
6
Data type Unsigned16
7
Data type Unsigned32
10
Data type octet string
40
Record type Unsigned8, Unsigned16
41
Record type Unsigned8, 2 x Unsigned16
...
49
Record type Unsigned8, 10 x Unsigned16
60
Record type Unsigned8, Unsigned32
61
Record type Unsigned8, 2 x Unsigned32
...
69
Record type Unsigned8, 10 x Unsigned32
70
Record type Unsigned8, Unsigned16
71
Record type 2 x (Unsigned8, Unsigned16)
...
79
Record type 10 x (Unsigned8, Unsigned16)
80
Record type Unsigned8, Unsigned32
81
Record type 2 x (Unsigned8, Unsigned32)
...
89
Record type 10 x (Unsigned8, Unsigned32)
500
2 byte PLC interface
1000-1254
Programmed inputs/outputs
10000-10643
Diagnostic messages
15000-15643
Events for diagnostic messages
Miscellaneous
DP/FMS operation
The BK 3000 always supports both DP and FMS operation up to
1.5 Mbaud. The BK 3100 supports the operation set in register 16 in table
0 of the bus coupler up to 12 Mbaud:
0
DP/FMS operation (default)
1
DP operation
2
FMS operation
In either pure DP operation or pure FMS operation it is possible for more
input and output data and/or more connections can be defined (see
above).
Min. TSDR
The bus coupler’s minimum answer time can be set through register 17 in
table 0 of the bus coupler. The default value is 11 (bit times), but values
from 11 to 255 are possible.
Important:
some FMS Masters are too slow to react to the bus coupler’s default
answer time. The bus coupler’s answer time can however with the KS2000
be changed via the serial interface. In such cases, the min. TSDR should
be changed as follows:
Baud rate
min. TSDR
9.6 kbaud
30
19.2 kbaud
60
93.75 kbaud
125
187.5 kbaud
250
greater than 187.5 kbaud 255