Appendix, Example: process image in the bus coupler – BECKHOFF BK3000 User Manual
Page 38
Appendix
38
BK3xxx/LC3100
Appendix
Example: process image in the bus coupler
The following example will illustrate the assignment of input/output
channels to the process image. Our sample construction is to consist of the
following bus terminal components (this example is related to the standard
bus coupler; no analogue terminals can be configured for the Economy and
LowCost couplers):
For this configuration
Position
Function component on the track
the bus coupler will create
POS01
Bus coupler
the list of assignments
POS02
2-channel digital input
shown below
POS03
2-channel digital input
POS04
2-channel digital input
POS05
2-channel digital input
POS06
2-channel digital input
POS07
2-channel digital output
POS08
2-channel digital output
POS09
2-channel digital output
POS10
2-channel analog input
POS11
2-channel analog output
POS12
2-channel analog output
POS13
2-channel analog input
POS14
Power input terminal
POS15
2-channel digital input
POS16
2-channel digital input
POS17
2-channel digital input
POS18
2-channel digital output
POS19
2-channel digital output
POS20
2-channel analog output
POS21
End terminal
Besides transfer of the user information signal, when using analog
terminals the control/status byte is also available via the process image by
parameterisation of a three-byte channel (see PROFIBUS-DP).
Area for byte-oriented
data, analog outputs
Relative byte
address
Bit position
Process image in
the control unit
Position in the
block
0, 1
none
%QB0, %QB1
POS11
2, 3
none
%QB2, %QB3
POS11
4, 5
none
%QB4, %QB5
POS12
6, 7,
none
%QB6, %QB7
POS12
8, 9
none
%QB8, %QB9
POS20
10, 11
none
%QB10, %QB11
POS20