Basic information
22
BK3xxx/LC3100
Fieldbus errors in the LC3100
I/O-RUN
BF
RUN
Meaning
Remedy
on
off
on
Operating state: RUN
Inputs are read and outputs are set.
Everything is operating correctly
on
on
on,
blinking
1. Bus activity, but slave is not yet
parameterised
2. Bus error in which the outputs
a.) become 0
b.) remain unchanged
- Start master
- Check parameters
(-> Diagnostics data, BF-LED)
- Check configuration
(-> Diagnostics data, BF-LED)
off
off
on
Terminal bus cycles synchronised
DP-watchdog switched off, no exchange
of data
PLC is in STOP mode
off
on
off,
blinking
No bus activity
- Start master
- Check bus cable
off
on
on
Bus error, reaction
Terminal bus cycles are stopped
- Start master
- Check parameters
(-> Diagnostics data, BF-LED)
- Check configuration
(-> Diagnostics data, BF-LED)
Run times and reaction times
Transfer of the signals from the input to the controller and from the
controller to the outputs requires a run time. This is composed of various
components. Transfer from the controller to the master, transfer through
the Profibus and transfer from the bus coupler to the outputs. This applies
analogously to the return distance.
Controller / Master
Please refer to the data provided by the master manufacturer for details of
the reaction time from the controller to the master. These times are
comparatively short and normally do not need to be considered.
The reaction time t
DP
on the Profibus is composed of the following. The
constants A, B and T
BYTE
depend on the baud rate.
7
T
DP
= Constant A
+ (Constant B + (Number of E/A-Byte x T
BYTE
))
[Slave 1]
+ (Constant B + (Number of E/A-Byte x T
BYTE
))
[Slave 2]
+ (Constant B + (Number of E/A-Byte x T
BYTE
))
[Slave 3]
+ ...
[Slave ]
+ (Constant B + (Number of E/A-Byte x T
BYTE
))
[Slave n]
Baud rate
Constant A
(in ms)
Constant B
(in ms)
T
BYTE
(in ms)
9,6 kBaud
64,5
25,6
1,15
19,2 kBaud
32,3
12,8
0,573
93,75 kBaud
6,6
2,62
0,118
187,5 kBaud
3,3
1,31
0,059
500 kBaud
1,6
0,49
0,022
1,5 MBaud
0,67
0,164
0,00733
3 MBaud
0,436
0,085
0,00367
6 MBaud
0,27
0,044
0,00183
12 MBaud
0,191
0,024
0,00092
i
Note
Pay attention to the special restrictions when using an ET200U or S5-95U
in one system. In certain circumstances, cycle times may be clearly
prolonged and more than 1.5 Mbaud is not possible.