Setting of interface parameter – BECKHOFF CX50x0 User Manual
Page 38
Notes on the documentation
36
CX50x0 - Hardware Documentation
RS422/RS485 connections (CX50x0-N031)
The CX50x0-N030 system interface provides an RS422 or RS 485 interface, COM1 (X300). It is implemented on a 9-
pole Sub-D socket strip. If more than one interface is required the system can be extended via the Terminal Bus (K-
or E-bus) or Bus Terminals (KL/EL6021) which provide serial interfaces. The pin assignment is shown at the bottom
of the page.
The maximum baud rate on both channels is 115 kbit. The interface parameters are set via the operating system or
from the PLC program.
COM interface (socket)
Pin assignment of the COM interface
PIN
Signal
Typ
Beschreibung
2
TxD+
Data-Out +
Transmit 422
3
TxD+
Data-In +
Receive 422
5 GND
Ground
Ground
6
VCC VCC +5V
7
TxD-
Data-Out -
Transmit 422
8 TxD+
Data-In
-
Receive
422
For RS 485 pins 2 and 3 (data +) must be connected, and pins 7 and 8 (data -).
Setting of interface parameter
RS485, without echo, end-point (termination) default setting
Function
Status
Echo on
Off
Echo off
On
Auto send on
On
Always send on
Off
Auto receive on
On
Alway receive on
Off
Term on
On
Term on
On
Note
Change the parameter
If there is a need for other settings please contact our service department.