beautypg.com

Settings dip switches rs485 – BECKHOFF CX1000 User Manual

Page 24

background image

Product Overview

22

Embedded PC

CX1000-N005 connections

The system interface CX1000-N005 contains two RS422, RS485 interfaces, COM2 and COM3 (9 pin Sub-D plug
connector).
The maximum baud rate on both channels is 115 kBit.

COM interface (plug):

Pin assignment of the COM interface:

PIN

Signal

Type

Description

2

TxD+

Data-Out +

Transmit 422

3

RxD+

Data-In +

Receive 422

5

GND

Ground

Ground

6

VCC

VCC

+5V

7

TxD-

Data-Out -

Transmit 422

8

RxD-

Data-In -

Receive 422

For RS 485 Pin 2 and 3 ( Data +) as well as Pin7 and 8 (Data -) have to be connected.

The pins not listed are not used.

Settings DIP switches RS485:

RS485 without Echo, End-Point ( Terminated) DEFAULT SETTING

DIP

Status

Function

1

off

Echo on

2

on

Echo off

3

on

Auto send on

4

off

Always send on

5

on

Auto receive on

6

off

Always receive on

7

on

Term on

8

on

Term on

RS485 with Echo, End-Point ( Terminated)

DIP

Status

Function

1

on

Echo on

2

off

Echo off

3

on

Auto send on

4

off

Always send on

5

off

Auto receive on

6

on

Always receive on

7

on

Term on

8

on

Term on