Basler Electric BE1-27 User Manual
Page 47

9170600990 Rev L
BE1-27/59 Testing
5-5
Step 4.
Set the time delay control for the function being tested to 01 (0.1 seconds). Press and
release S2 to assure that K1 is de-energized. Reset the timer. Press and release S1.
RESULT: The timer displays a response time, dependent on timing type, as indicated in Column 1 of
Step 5.
Press and release S2. Set the time delay control for the function being tested to 99 (9.9
seconds). Reset the timer. Press and release S1.
RESULT: The timer displays a response time, dependent on timing type, as indicated in Column 2 of
Step 6.
Repeat Steps 1 through 5, as necessary, for each function’s time delay control.
This concludes the operational test procedure.