Resistive ratings, Inductive ratings, Current operated targets – Basler Electric BE1-27 User Manual
Page 13: Output, Contacts, Power, Supply -5, Target, Indicators, Type

9170600990 Rev L
BE1-27/59 General Information
1-5
Output Contacts
120 Vac ............................................. Make, break, and carry 7 Aac continuously
Resistive Ratings
250 Vdc ............................................. Make and carry 30 Adc for 0.2 s, carry 7 Adc continuously,
break 0.3 Adc
500 Vdc ............................................. Make and carry 15 Adc for 0.2 s, carry 7 Adc continuously,
break 0.3 Adc
120 Vac, 125 Vdc, 250 Vdc .............. Break 0.3 A (L/R = 0.04)
Inductive Ratings
Power Supply
Power supply types and specifications are listed in Table 1-1.
Table 1-1. Power Supply Ratings
Type
Nominal
Input Voltage
Input Voltage
Range
Burden at
Nominal
K (midrange)
48 Vdc
24 to 150 Vdc
3.8 W
J (midrange)
125 Vdc
24 to 150 Vdc
4.0 W
120 Vac
90 to 132 Vac
17.1 VA
L (low range)
24 Vdc
12 to 32 Vdc *
3.9 W
Y (midrange)
48 Vdc
24 to 150 Vdc
3.8 W
125 Vdc
24 to 150 Vdc
4.0 W
Z (high range)
250 Vdc
68 to 280 Vdc
4.1 W
240 Vac
90 to 270 Vac
28.4 VA
*
Type L power supply initially requires 14 Vdc to begin operating. Once operating, the input voltage may
be reduced to 12 Vdc and operation will continue.
Target Indicators
Electronically latched, manually reset target indicators are optionally available to indicate closure of the
trip output contacts. Either internally operated or current operated targets may be specified. Internally
operated targets should be selected when normally closed (NC) output contacts are specified.
Minimum Rating ................................ 200 mA flowing through the trip circuit
Current Operated Targets
Continuous Rating ............................ 3 A
1 Second Rating ............................... 30 A
2 Minute Rating................................. 7 A
Type Tests
Shock ................................................ Withstands 15 G in each of three mutually perpendicular planes
without structural damage or performance degradation.
Vibration ............................................ Withstands 2 G in each of three mutually perpendicular planes,
swept over the range of 10 to 500 Hz for a total of six sweeps, 15
minutes each sweep, without structural damage or degradation of
performance.
Dielectric Strength ............................ Tested in accordance with IEC 255-5 and IEEE C37.90: 2,000 Vac
applied for 1 min
Impulse Test ..................................... Qualified to IEC 255-5