4 • installation, Introduction, Relay operating guidelines and precautions – Basler Electric BE1-47N User Manual
Page 25: Mounting, Section 4, Installation -1

9170400990 Rev J
BE1-47N Installation
4-1
SECTION 4 • INSTALLATION
Introduction
BE1-47N relays are shipped in sturdy cartons to prevent damage during transit. Upon receipt of a relay,
check the model and style number against the requisition and packing list to see that they agree. Inspect
the relay for shipping damage. If there is evidence of damage, file a claim with the carrier, and notify your
sales representative or Basler Electric.
If the relay will not be installed immediately, store it in its original shipping carton in a moisture- and dust-
free environment. Before placing the relay in service, it is recommended that the test procedures of
Section 5, Testing be performed.
Relay Operating Guidelines and Precautions
Before installing or operating the relay, note the following guidelines and precautions.
•
For proper current operated target operation, a minimum current of 200 milliamperes must flow
through the output trip circuit.
•
If a wiring insulation test is required, remove the connection plugs and withdraw the relay from its
case.
CAUTION
When the connection plugs are removed, the relay is disconnected from the
operating circuit and will not provide system protection. Always be sure that
external operating (monitored) conditions are stable before removing a relay
for inspection, test, or service.
NOTE
Be sure that the relay is hard-wired to earth ground with no smaller than 12
AWG copper wire attached to the ground terminal on the rear of the case.
When the relay is configured in a system with other devices, it is
recommended to use a separate lead to the ground bus from each device.
Mounting
Because the relay is of solid-state design, it does not have to be mounted vertically. Any convenient
mounting angle may be chosen.
Relay outline dimensions and panel drilling diagrams are shown in Figures 4-1 through 4-7. Dimensions
are shown in inches with millimeters in parenthesis.